background image

 

These are represented by a graphic on the LCD: 

 

 

The rectifier 

  converts the incoming AC power into DC. In doing so, surge suppressors 

and filters remove any noise and damaging surges. The rectifier is Power Factor Corrected 
(PFC) which means the UPS presents itself as a purely resistive load, ensuring the UPS has no 
detrimental effects on power quality elsewhere in the building. The rectifier performs two 
functions. The first is to provide the DC for the inverter, and the second is to provide a charging 
voltage (and current) for the battery.   

The battery 

  has two circuits connected to it. The first is the charger that has an 

adjustable battery charge current to allow extra battery packs to be connected without 
compromising on recharge time. The second is a DC-DC converter that converts the battery DC 
voltage to the DC bus voltage to feed the inverter when running on battery operation. 

The inverter 

  converts the DC bus voltage into the AC output voltage. It is a high 

frequency, highly efficient design that utilizes PWM driven IGBTs to create a pure sine wave 
output via the output low pass filter. The output voltage is constantly monitored and adjusted 
for differing load levels to maintain a highly stable output. The voltage can be adjusted 
depending upon requirements. 
 
See section 4.6 for details of operating modes and graphical representation on the LCD.   
 

 

The VFI1000QS utilises Power Inspired’s propriety Advanced Speed 
Control (ASC) cooling system. Utilising super quiet fans the fan 
speed is set according to actual cooling requirements. Thus, at low 
loads and temperatures the fans will run at low speeds making the 
units practically inaudible. This makes the VFI1000QS suitable for 
applications where the highest degrees of power quality and 
protection are required but where unit silence is paramount.   
 

 

2.3.

 

Cooling 

Summary of Contents for VFI1000QS

Page 1: ...VFI1000QS Online Double Conversion Silent UPS System Version 1 0 User Manual...

Page 2: ...on 6 3 5 Tower Installation 7 3 6 UPS Location 7 3 7 UPS Connections 8 3 8 Starting Up the VFI1000QS 10 3 9 Start up on battery cold start 10 3 10 Switching off the UPS 10 3 11 Install software Option...

Page 3: ...let which should be easily accessible and close to the UPS system Use supplied input mains cord Please use only BS Kite marked VDE tested and or CE marked power cables to connect the loads to the UPS...

Page 4: ...mutilate batteries Released electrolyte is harmful to the skin and eyes It may be toxic Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures...

Page 5: ...voltage window Noise Transients Harmonics Distortions on the input mains voltage are not transferred to the load The load is powered from the UPS inverter at all times which is ReGenerating a new AC...

Page 6: ...o the DC bus voltage to feed the inverter when running on battery operation The inverter converts the DC bus voltage into the AC output voltage It is a high frequency highly efficient design that util...

Page 7: ...Be sure that nothing inside the package is damaged Please keep the original packaging in a safe place for future use For safety the UPS is shipped out from the factory without connecting the battery...

Page 8: ...lation to position this UPS Step 1 Step 2 Fit the rack ears observing left marked L and right marked R positions when looking at the unit When in a rack the VFI1000QS must be supported by a shelf or r...

Page 9: ...15 C to 25 C for optimal operation For every 2 C above 30 C the UPS will need to be derated by 10 of nominal capacity at full load The highest working temperature requirement for UPS operation is 40 C...

Page 10: ...ver current protection in place not exceeding 16A e g a circuit breaker Note Check if the site wiring fault indicator lights up in LCD panel It will be illuminated when the UPS is plugged into an impr...

Page 11: ...the card is properly located within the grooves in the housing before attempting to fully engage 3 7 5 Network connection Network Fax Phone surge port Connect a single modem phone fax line into surge...

Page 12: ...ton for at least 2 seconds to turn off the UPS 2 The UPS will enter standby or bypass mode if AC power is present or switch off if switched off when in battery mode For optimal computer system protect...

Page 13: ...es Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the battery box by removing two screws on the...

Page 14: ...inside of UPS Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below diagram Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side...

Page 15: ...ction key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage outp...

Page 16: ...abled Output Load information Indicate the input voltage input frequency input current battery voltage battery current battery capacity ambient temperature output voltage output frequency load current...

Page 17: ...tery level by 0 24 25 49 50 74 and 75 100 Indicates low battery Battery Mode Sounding every 5 seconds Low Battery Sounding every 2 seconds Overload Sounding every second Fault Continuously sounding By...

Page 18: ...OIT Output isolation transformer EAT Estimated autonomy time RAT Running autonomy time CF Converter ON ON SD Shut down OI Over input current EP EPO TP Temperature CH Charger FU Bypass frequency unsta...

Page 19: ...meter 2 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Output frequency setting Interface Setting Param...

Page 20: ...fault 12V 06 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Default...

Page 21: ...low loss point from 55Hz to 59Hz Default 57 0Hz 09 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programm...

Page 22: ...00 10 100 150 12 14 Charger boost voltage setting Interface Setting Parameter 2 Set up the charger boost voltage 2 25 2 40 setting the charger boost voltage from 2 25 V cell to 2 40V cell Default 2 36...

Page 23: ...tting for autonomy time EAT If EAT is selected it will display the remaining autonomy time Default RAT If RAT is selected it will show accumulated autonomy time so far 19 Acceptable input voltage rang...

Page 24: ...S can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure the UPS...

Page 25: ...ng 2 beep every 10 seconds Battery is not connected Over Charge Sounding every 2 seconds Site wiring fault Sounding every 2 seconds EPO enable Sounding every 2 seconds Over temperature Sounding every...

Page 26: ...onnected Check if all batteries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer F...

Page 27: ...fully charged Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault cod...

Page 28: ...operation Batteries are specified for 200 cycles Stored or remained off charge in a depleted state Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replac...

Page 29: ...ttery ECO Mode 96 full charged battery Battery Mode 88 BATTERY Battery Type 12V 9AH Numbers 4 Recharge Time 3 hours recover to 95 capacity for internal battery 2A charging current Charging Current 200...

Page 30: ...V Capacity 18Ah Dimensions DxWxH mm 480 x 438 x 88 Net Weight kgs 29 Advanced Speed Control ASC Specification Fan Qty 2 Type PWM Controlled 80mm Minimum RPM 450 Maximum RPM 2200 Noise Output Minimum 1...

Page 31: ...TY WILL ARISE OUT OF PI RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND RE...

Reviews: