18
05: ECO voltage range setting
Interface
Setting
Parameter 2:
Set the acceptable high voltage point and
low voltage point for ECO mode by pressing Down key or Up
key.
HLS:
High loss voltage in ECO mode
in parameter 2.
The setting range in parameter 3 is from +7V to +24V of the
nominal voltage. (Default: +12V)
LLS:
Low loss voltage in ECO mode in parameter 2.
The setting range in parameter 3 is from -7V to -24V of the
nominal voltage.
(Default: -12V)
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 2:
Enable or disable Bypass function. You may
choose the following two options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
07: Bypass voltage range setting
Interface
Setting
Parameter 2:
Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing
the Down key or Up key.
HLS:
Bypass high voltage point
230-264:
setting the high voltage point in parameter 3
from 230Vac to 264Vac. (Default: 264Vac)
LLS:
Bypass low voltage point
170-220:
setting the low voltage point in parameter 3 from
170Vac to 220Vac. (Default: 170Vac)