11.5.9.B
[FOPN] Valve Full Open Control (default: 0.3)
FOPN
0.3
0-9.9
The valve can be fully open manually. And it is possible to change 0% to 9.9%. For reference, 0.1%
means that the positioner responds to 0.016mA. Therefore, the standard value of 0.3% means that
a valve is fully open at 19.952mA.
11.5.9.C
[OUT] Setting of Output Signal (default: 4 - 20mA)
OUT
4 - 20
20 - 4
4 – 20mA is a standard factory setting. It’s available to change to 20 – 4mA reversely.
11.5.9.D
[SPLT] Split Range Setting (default: 4-20)
SPLT
4-20
4-12
12-20
Split range can be set to 4-12mA or 12-20mA.
11.5.9.E
[LCD] Change of Display Position on LCD
LCD
FOR
REV
LCD is to change the display position on LCD in case that the positioner is installed upside down.
LCD : FOR
LCD : FOR
LCD : REV