SS3L / SS3R Series
www.powergenex.com
35
11.4.5.
Auto-Calibration Mode
AUTO
TUNE
RSET
STEN
COLD
If necessary, initialize all setting values to the original values set after auto-calibration or return
them to the factory setting values.
11.4.5.A
Performing Auto-Calibration
11.4.5.B
Initializing Setting Values (RESET)
All setting values return to the standard factory setting values.
11.4.5.C
Re-adjustment of Zero & Span (STEN)
Only Zero and Span is re-set without changing other values set after auto-calibration.
11.4.5.D
COLD (Re-booting)
Restarts the program without changing any settings
① Reverse acting (RA) is a standard factory setting. Even if air lines are connected
wrongly by mistake, the SS2 positioner detects automatically and performs auto-
calibration for direct acting (DA).
② If the actuator doesn’t work with 4-20mA input signal properly, change air lines
of OUT1 and OUT2 with each other and perform auto-calibration again.
③ For a reverse acting type (RA), a countdown will begin like RA-5-4-3-2-1-END.
For a direct acting type (DA), a countdown will begin like 5-RA-DA-4-3-2-1-END.