SS3L / SS3R Series
www.powergenex.com
44
11.5.9.
SUB Parameter
Ref.
Parameter
Description
Function
Default
11.5.9.A
Shut-off
0…9.9%
0.3%
11.5.9.B
Full-open
0…9.9%
0.3%
11.5.9.C
Output signal
4…20mA or 20…4mA
4…20mA
11.5.9.D
Split range
4…12mA or 12…20mA
4…20mA
11.5.9.E
Change of display
position on LCD
Forward or reverse direction
FOR
11.5.9.F
Alarm limit low,
high
AL1L/AL1H, AL2L/AL2H
0…10%,
90…105%
11.5.9.G
IN4M / IN20
sets to values relating to 4-
20mA input signal
Factory setting
11.5.9.H
FB4M / FB20
sets to values relating to 4-
20mA output signal
Factory setting
11.5.9.I
HART
polling address
0…15
0
11.5.9.J
Partial stroke
testing
checks a valve status
OFF
11.5.9.A
[SHUT] Valve Shut-off Control (default: 0.3)
SHUT
0.3
0-9.9
It is a safety function to close a valve completely. And it is possible to change 0% to 9.9%. For
reference, 0.1% means that the positioner responds to 0.016mA. Therefore, the standard value of
0.3% means that a valve is closed at 4.048mA completely.
Note that the PST function (Partial Stroke Testing) is loaded at the factory on demand
only when requested.