SS3L / SS3R Series
www.powergenex.com
42
11.5.7.
[CTRL] – Control Speed Adjustment
CTRL ⇒ SPED
GAP
KISP
GNLT
CNLT
HDGP
11.5.7.A
[SPED] – Response Speed Adjustment (default: 1000)
SPED
1…1000
This is to adjust the response speed of the actuator. (Min: 1, Max: 1000)
11.5.7.B
[GAP] – (default: 100)
GAP
100…999
This is to secure a more stable control by adding more PID values.
11.5.7.C
[KISP] – kI-Gain Speed(default: 100)
KISP
AUTO
0-30
As KSIP is set automatically during auto-calibration process, it is not necessary to change
manually.
11.5.7.D
[GNLT] – Gap Control Limit (default: automatically-set)
GNLT
AUTO
100-650
GNLT is to control a whole operating range. If the valve comes within
±
3% of input signal, GNLT
works with 1/2 value of CNLT for a safer control. In case that a hunting or oscillation problem
happens around the position related to the input signal, a safer control can be accomplished by
lowering GNLT.