SS2L / SS2R Series
www.powergenex.com
32
11.3 Parameters
11.3.1 Main Parameters
Ref.
Parameter
Description
Function
Default
11.5.1 (P. 36)
INPU
Input signal
4…20mA or 20…4mA
4…20mA
11.5.2 (P. 36)
R / DA
RA / DA
Reverse acting or direct acting
RA
11.5.3 (P. 36)
L / E.Q /
QOPN/USER
Characteristic
Linear, E.Q. % (1:25 or 1:50),Quick open
or User set (17points)
Linear
11.5.4 (P. 38)
SPAN
Span adjustment
0…100%
100%
11.5.5 (P. 38)
ZERO
Zero adjustment
0…99%
0%
11.5.6 (P. 39)
PID
P-GN / I-GN
/ D-GN
Proportional / Integral
/ Differential gain value
Auto-set
11.5.7 (P. 41)
CTRL
SPED / SWST / CNLT
/ GCNL
See 11.3.2 CTRL
ㆍ
11.5.8 (P. 42)
DEAD
Dead band
0…9.99%
0.5%
11.5.9 (P. 43)
FDGN
D-gain setting for
hard mode
D-Gain setting for hard mode
Auto-set
11.5.10 (P. 43)
C/MD
NORM / HARD /
SMAL
Standard actuator, strong valve packing friction,
small actuator or angle seat valve
NORM
11.5.11 (P. 44)
SUB
Sub-Parameters
See 11.3.3 SUB
ㆍ
11.3.2 CTRL - Parameters (control speed adjustment)
Ref.
Parameter
Description
Function
Default
11.5.7.A (P. 41)
SPED
Response speed
1…1000
1000
11.5.7.B (P. 41)
SWST
Slow start
Smooth operation
Auto-set
11.5.7.C (P. 42)
CNTL
Control limit
50…1250
Auto-set
11.5.7.D (P. 42)
GCNL
Gap Control limit
100…650
Auto-set
11.5.7.E
SRPS
Control status
Auto-set
11.3.3 SUB - Parameter
Ref.
Parameter
Description
Function
Default
11.5.11.A (P. 44)
SHUT
Shut-off
0…9.9%
0.3%
11.5.11.B (P. 45)
FOPN
Full-open
0…9.9%
0.3%
11.5.11.C (P. 45)
OUT
Output signal
4…20mA or 20…4mA
4…20mA
11.5.11.D (P. 45)
SPLT
Split range
4…12mA or 12…20mA
4…20mA
11.5.11.E (P. 45)
DIGN
Display place
Movement to one or two decimal
places
1
11.5.11.F (P. 46)
ALAM
Alarm limit low, high
AL1L/AL1H, AL2L/AL2H
0…10%, 90…105%
11.5.11.G (P. 48)
ICAL
IN4M / IN20
sets the values in accordance with
4~20mA input signals
Factory setting
11.5.11.H (P. 48)
FCAL
FB4M / FB20
sets the values in accordance with
4~20mA output signals
Factory setting
11.5.11.I (P. 49)
POLL
HART Polling Address
0…15
0
11.5.11.J (P. 49)
PST
Partial Stroke Test
checks a valve status
OFF