SS2L / SS2R Series
www.powergenex.com
25
9.2 Measuring Output Signal
9.2.1 With mA loop calibrator
9.2.2 With multi-meter
Zero and span of position feedback (4-20mA output signal) are set automatically during
auto-calibration process.
9.3 Wiring Alarm Limits
24VDC should be supplied for alarm limits.
9.4 HART Connection
Note that wires for HART communication should be connected to terminals No. 1 and
No. 2 together with wires for input signals. For reference, there is no distinction in +
and – between HART wires.
9.5 Profibus PA / Fieldbus Connection
Make sure of + and – when connecting wires.
Position Transmitter Specifications
Output signal
4 – 20mA, 2-wire
Power supply
12 – 30 VDC
Output current limit
30mA DC
Linearity
±0.75% F.S
Operating temperature
-20 ~ +80℃