SS2L / SS2R Series
www.powergenex.com
53
11.5.11.K [ADDR] – Manual Setting of Profibus PA Address (default: 126)
ADDR
126
1 ~ 125
This is to change the Profibus PA address to 1 – 125 manually on the site. “126” is a factory
setting.
12. Maintenance / Service
12.1 Preliminary Check Points
12.1.1 Voltage
- The positioner commonly requires 4-20mA @ 24VDC for operation.
- Voltage drop (impedance): Without HART – 8.7VDC (435Ω @ 20mA)
With HART – 9.4VDC (470Ω @ 20mA)
12.1.2 Electrical Connections
Check polarities (+, -) of 4-20mA input signal definitely and make the electrical connections.
12.1.3 Pneumatic Connections (see 8.1, 8.2)
12.1.4 Supply Air Quality
A supply air should be definitely clean and compressed free of water, moisture or oil in
conformance with IEC 770 and ISA-7.0.01.
12.2 Module Parts
① RTQ Coil Assembly (spare part No. 12)
② Pilot Valve Assembly (spare part No. 5)
③ PCB Control Board Assembly (spare part No. 3)
12.3 Structure of Gauge Block
UP
DN
ENT
Select ADDR
ENT
UP
DN
Change
Profibus address