WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property
damage. Refer to the burner manual for assistance or additional information consult a qualified
installer, service agency or the gas supplier.
Do not store or use gasoline or other flammable liquids and vapors in the vicinity of this or any other
appliance.
START UP
Preparation for Start Up
1) Ensure that the system is in working order. If
heat exchanger is a boiler, ensure that proper
water level is available.
2) For oil burner make sure that the oil tank has
an adequate fuel level and that the fuel is the
proper grade.
3) Set the burner control panel switch to the OFF
position.
4) Combination Gas/Oil burner: set the fuel
selector switch to the fuel to be burned.
5) Turn the thermostat or operating control down
to its lowest setting.
6) Check fuses and replace as necessary.
7) Depress the flame safeguard programming
control reset button.
Start Up – Gas Burner
1) Manually open and close the main gas shut off
cock, leak test cock and pilot cock to determine
that they operate freely. Open all three cocks.
(Reset low gas pressure switch if supplied).
2) Set the main power switch and burner panel
control switch to the ON position. Wait 30
seconds and turn up thermostat or operating
control to the desired setting.
3) The burner blower motor will start and after a
suitable pre-purge period (this will vary with the
type of flame safeguard control supplied – but
will usually be minimum of 30 seconds to a
maximum of 90 seconds) the burner pilot will
light, after which the main flame will be
established.
4) If the system does not respond properly,
contact your qualified burner service company.
5) When burning gas on a combination gas/oil unit
that has a blower motor driven oil pump, open
all oil line valves. Oil must circulate through the
oil pump, even when burning gas.
Start Up – Oil Burner
1) Open all valves in oil lines.
2) If pilot gas ignition system is supplied: open and
close the pilot gas cock to determine that it is
operating freely. Open the pilot gas cock.
3) Set the main power switch and burner panel
control switch to the ON position. Wait 30
seconds and turn up thermostat or operating
control to the desired setting.
4) The burner blower motor will start. Depending
upon the type of flame safeguard control
supplied, the fuel ignition system may energize
within 1 or 2 seconds after the blower motor
starts or could be as long as 90 seconds.
5) If the system does not respond properly,
contact you qualified burner service company.
EXTENDED SHUT DOWN
1) Place main power switch and burner control
panel switch in the OFF position.
2) Close all valves in gas lines.
3) Cover burner to protect it from dust and
dampness.
FOR YOUR SAFETY
If you smell gas
:
1) Open windows
2) Do not touch electrical switches
3) Extinguish any open flame
4) Call you gas supplier immediately
IMPORTANT PRECAUTIONS
1) Never attempt to light burner with paper or
other materials.
2) Never experiment with the burner.
3) Never change the fuel or air adjustments
without consulting with the burner service
company.
4) Never attempt to light the burner if combustion
chamber contains any unburned fuel or gases.
5) Never throw waste paper, rags, garbage or
other waste materials into the combustion
chamber.
6) Never wash out heating equipment room
without first covering the burner with waterproof
material.
MAINTENANCE
Burner should be maintained and serviced by a
qualified service agent. See service and
maintenance section of the manual for suggestions
on periodic maintenance and service.