Item
Frequency
Checked By
Remarks
Gages, monitors and indicators
Daily
Operator
Make visual inspection and record readings in log
Weekly
Operator
Verify heat exchanger manufacture’s settings
Semiannually
Service Technician
Verify heat exchanger manufacture’s settings
Annually
Service Technician
Check with combustion test
Flue, vent, stack or outlet damper
Monthly
Operator
Make visual inspection of linkage
check for proper operation
Combustion air
Monthly
Operator
Check that all sources remain clean and open
Ignition System
Weekly
Operator
Make visual inspection
Check flame signal strength
(see Combustion Safety Controls)
Flue, vent, stack or outlet damper
Monthly
Operator
Make visual inspection of linkage
Check for proper operation
Weekly
Operator
Open limit switch-make aural and visual check
Check valve position indicators
Check fuel meters if so fitted
Annually
Service Technician
Perform leakage tests
(refer to valve manufacturer’s instructions)
Flame failure
Weekly
Operator
Close manual fuel supply for (1) pilot and (2) main
fuels and
check safety shutdown timing and log
Flame signal strength
Weekly
Operator
If flame signal meter installed, read and log for both
pilot and main flames
Notify service organization if readings are very high,
very low, or fluctuating
(Refer to flame safeguard manufacturer’s
instructions)
Pilot turndown tests
As required/annually
Service Technician
Required after any adjustments to flame scanner
mount or pilot burner
(Refer to flame safeguard manufacturer’s
instruction)
Pilot signal
As required/annually
Service Technician
Verify that the scanner does not pick up the spark or
the glow from the refractory
High limit safety control
Annually
Service Technician
Refer to heat exchanger manufacturer’s instructions
Operating control
Annually
Service Technician
Refer to heat exchanger manufacturer’s Instructions
Draft, fan, air pressure,and damper
Monthly
Operator
Refer to this manual and control manufacturer’s
instructions
High & low gas pressure interlocks
Monthly
Operator
Refer to instructions in this manual
Low oil pressure interlocks
Monthly
Operator
Refer to instructions in this manual
Fuel valve interlock switch
Annually
Service Technician
Refer to valve manufacturer’s instructions
Purge switch
Annually
Service Technician
Refer to fuel/air control motor manufacturer’s
instructions
Low fire start interlock
Annually
Service Technician
Refer to fuel/air control motor manufacturer’s
instructions
Automatic changeover control
(dual fuel)
Annually
Service Technician
Under supervision of gas utility
Remove oil drawer assembly
Annually
Service Technician
Remove and clean
Blower motor and blower wheel
Annually
Service Technician
Remove and clean as necessary
Gas pilot assembly
Annually
Service Technician
Remove and clean as necessary
Air compressor
Monthly
Operator
Check oil level and fill as required
Pilot and main gas or oil valve
Firing rate control