• Before each use, make sure the engine’s oil and gas levels are adequate. If

necessary, fill the crankcase until the oil level is even with the oil fill hole
and/or fill the fuel tank.

• Before each use, remove all debris with a soft brush, rag, or vacuum.
• Lubricate all moving parts using a premium quality, lightweight machine oil.
• Every 50 hours of use, drain the old engine oil and replace with a high a

high quality SAE 10W30 grade engine oil.

• Every 300 hours of use, have a qualified, certified technician perform

thorough maintenance on the generator and engine.

• For long term storage, either drain fuel into suitable container or add a fuel

preservative/stabilizer (not included) to prevent fuel breakdown.

Installation
NOTE: PRIOR TO POWERING TOOLS AND EQUIPMENT MAKE SURE THE GENERATOR’S RATED

VOLTAGE, WATTAGE AND AMPERAGE CAPACITY IS ADEQUATE TO SUPPLY ALL
ELECTRICAL LOADS THAT THE UNIT WILL POWER. IF POWERING EXCEEDS THE
GENERATOR’S CAPACITY, IT MAY BE NECESSARY TO GROUP ONE OR MORE OF THE TOOLS
AND/OR EQUIPMENT FOR CONNECTION TO A SEPARATE GENERATOR.

Electrical and other permits may be required for the installation of emergency power systems. Investigate your
local building and electrical codes before installing this unit. Installation must be completed by licensed
contractors.
WARNING! THE GENERATOR WEIGHS APPROXIMATELY 100 POUNDS. USE CARE AND THE PROPER

LIFTING OR HOISTING EQUIPMENT WHEN MOVING IT TO THE INSTALLATION
LOCATION. ALWAYS CONNECT HOIST LINES TO THE FRAME OF THE GENERATOR.

General Location
• Make sure to locate and install the generator outdoors where cooling air is readily available.
• Install the generator so that the air inlets and outlets are not blocked by obstructions such as bushes, trees, or

snow drifts. Locating it in the path of heavy winds or snowdrifts may require the placement of a barrier for
protection. In normal weather conditions, the air vent should face the prevailing wind direction.

• Install the generator on a concrete slab or other area where rain drainage or flood waters can not reach it.
• Generator placement should allow four feet of access to all sides for maintenance. 
• Place the generator as close as possible to the electrical tools and equipment being powered to reduce the length

of extension cords.

Supporting and Mounting
Mount the generator on a concrete slab capable of supporting the weight of the generator. The slab must extend on
all sides beyond the frame by at least one foot. Contact a cement contractor for slab specifications if necessary.
Attach the frame to the concrete slab using 3/8” diameter expansion anchor bolts (not supplied).
Grounding
NOTE: IT IS RECOMMENDED THAT ONLY A TRAINED AND LICENSED ELECTRICIAN PERFORM THIS

PROCEDURE

Connect a #6 AWG grounding wire (not included) from the ground connector (8) on the generator to a grounding
rod (not included) that has been driven at least 24 inches deep into the earth. The grounding rod must be an earth-
driven copper or brass rod (electrode) which can adequately ground the generator.

Summary of Contents for 8142564

Page 1: ...2 800 Watt Generator 8142564 Owner s Manual...

Page 2: ...MALFUNCTION OF THE PRODUCT IS NOT COVERED BY PRINCESS AUTO Safety Guidelines This manual contains important information that you need to know and understand in order to protect YOUR SAFETY and to PREV...

Page 3: ...he engine and fuel tank Fuel vapors are explosive Keep grounded conductive objects such as tools away from exposed live electrical parts and connections to avoid sparking or arcing These events could...

Page 4: ...the power cord Keep power cords away from heat oil sharp edges or moving parts Replace damaged power cords immediately Damaged power cords increase the risk of electric shock When operating a power to...

Page 5: ...h is in its OFF position and disconnect the spark plug wire before making any adjustment changing accessories or storing the generator Such preventive safety measures reduce the risk of starting the g...

Page 6: ...capable of supporting the weight of the generator and all contents tools etc Install sound and weather proofing only when it is not raining or snowing to avoid trapping moisture within the generator...

Page 7: ...ot need a battery Assembly No assembly is required Operation NOTE THE PARTS LISTED ABOVE ARE HELPFUL FOR LOCATING THE CONTROLS MENTIONED BELOW CAUTION PRIOR TO FIRST USING THE GENERATOR THE ENGINE MUS...

Page 8: ...REAKER TO ITS ON POSITION RESTART THE GENERATOR AND CONTINUE POWERING THE REMAINING TOOLS AND EQUIPMENT 3 Note The Generator features an AC Non Fuse Circuit Breaker OFF position Turn the fuel valve to...

Page 9: ...is seated tighten with a spark plug in by hand to prevent cross threading 7 After the spark plug is seated tighten with a spark plug wrench to compress the washer NOTE THE SPARK PLUG MUST BE SECURELY...

Page 10: ...MOVING IT TO THE INSTALLATION LOCATION ALWAYS CONNECT HOIST LINES TO THE FRAME OF THE GENERATOR General Location Make sure to locate and install the generator outdoors where cooling air is readily ava...

Page 11: ...AC 3 spring grounded DC electrical no Gasoline engine Horsepower 6 0 HP Type 4 cycle OHV air cooled recoil start Displacement 171cc Oil capacity 0 6 quart 0 56 liter EPA approved yes Fuel Type Unleade...

Page 12: ...Bolt M6x25 63 Intake valve 64 Cylinder head 65 Bolt M6x85 66 Spark plug 67 Seal 68 Valve spring 69 Valve spring retainer 70 Valve cotter 71 Push rod 72 Push rod guide 73 Washer 6mm 74 Bolt 75 Rocker a...

Page 13: ...Parts Diagram...

Page 14: ...his certificate This certificate of conformity does not cover small non road engines imported prior to the effective date of the certificate This certificate of conformity is conditional upon complian...

Reviews: