MODELS:    

SE-1C08, SE-1C08HV, SE-1L08, SE-1L08HV, SE-1C40, SE-1C60, SE-1C80   

 

 

THREE PHASE CONNECTION & WRONG PHASE SEQUENCE INDICATOR

 

 

1)  

The right suggestion of the phases is a must for the normal function of the AVR. 

 

If the bars are marked 

(R, S, T) or (U, V, W) 

we follow the marks, if they are not, then we take 

 

the middle bar as 

"S" or "V" 

and connect it to terminal

 

"4"

 

of the AVR 

(important).

 

 

If we use current transformer its mandatory to connect it to this specific phase also 

(important).

 

2) 

On the AVR behind of the black terminal there is an orange neon lamp. When we start the generator  

     and it builds up voltage, if the orange neon lamp is lit up that means that the connection on the bars 

    

(R, T) or (U, W) 

is 

wrong 

and we must swap the position of two out-side wires 

(R-T) (or U-W).

 

3) 

The orange neon lamp absolutely must never lit-up 

(important).

 

 

 

                          CURRENT TRANSFORMER CONNECTION

 

 

 

1)

  It is 

necessary 

that the current transformer 

 

must 

be connected to the phase that also goes  

  to terminal 

"4" 

of the AVR. 

 

2) 

The current transformer has from one side  

  the letters 

K (or P1 

and on the other side 

L (or P2).

 

  From the side, 

K (or P1) 

enter the bar from the  

 

  generator and as it exits from the 

L (or P2) 

 

  it is going to ACB i.e. to main switch of the generator.  

    The two-connecting point of CT have the letters  

 

k-l (or s1-s2) 

and correspond respectively with 

7-6 

 

  of the AVR. 

 

       The current ratio of the CT is: 

 

       GENERATOR AMPERES  

           FOR FIVE AMPERES   

 

 

 

 

 

 

 

 

CONNECTING EXTERNAL VOLTAGE POTENTIOMETER  

 

The connection of the external pot does not need any polarity because it is doing the work of a rheostat. 

The value is always 500 Ohms.

 

 

EXCITATION POLARITY

 

 

The correct polarity of the feeding DC current to the exciter from the AVR J-K is a must otherwise the  

exciter will be demagnetized and will not build-up any voltage. If that happens we have to re-magnetize  

the exciter so 

after we disconnect the J-K cables from the AVR 

and while the engine has the right periods  

we connect (with the right polarity) a 

12V

 car battery to the generator side exciter J-K for about 

15 minutes

After the re-magnetization, we can restore the J-K connections to the AVR. 

 

 

 

 

 

WRONG CABLE CONNECTION MUST BE AVOIDED 

 