MODELS:    

SE-1C08, SE-1C08HV, SE-1L08, SE-1L08HV, SE-1C40, SE-1C60, SE-1C80   

 

 

U/F - 

Under Frequency Protection.

 It protects the generator from over-excitation current due to lower engine revs.  

To adjusting the “U/F” trimmer proceed as follows: 

 

The AVR comes with pre-configured 

Under Frequency 

protection. 

If re-adjusting is to be needed, proceed as follows: 

 

1.  

Turn clockwise the 

U/F

” 

trimmer all the way 

(25 turns). 

2.

  Start the engine and wait until voltage is built up. 

3.  

Reduce the fuel from the Governor until the periods  

     are 

10Hz

 less than the normal. (e.g. If the engine is running on 

50Hz

,  

     then the periods are to be reduced to 

40Hz

 and if the engine is running  

     on 

60Hz

, then the periods are to be reduced to 

50Hz.  

4.

  Turn anti-clockwise the 

U/F

” 

trimmer until the generator voltage   

     drops (n

ote that the generator voltage will also starts to drop). 

5.

  Restore generator to the normal state 

(50 or 60 Hz).

 

 

 

STAB 

- Stability.

 

It eliminates the voltage fluctuations. 

To adjusting the STAB trimmer, proceed as follows:

 

 

 

1.

 Turn anti-clockwise the Stab trimmer all the way (1 turn).  

2.

 Turn clockwise the STAB trimmer and set it just after the voltage     

    fluctuation stops. 

 * Setting the trimmer at a far clockwise position will decrease the  

    generator sensitivity. This may result to extensive voltage recovery time  

    due to the vast self-induction loads

 

 

 

 

VOLT - 

Voltage.

 Voltage adjustment. It co-operates with the external pot. 

To adjusting the VOLT trimmer, proceed as follows:

 

 

Since the engine has the right-periods (cycles), then the remote knob is adjusted to the middle position. 

Then the 

VOLT 

trimmer (which is located in the main unit) is adjusted until the right voltage is reached. 

All the above adjustments i.e. 

U/S, STAB, VOLT

, must be done without any load in the generator, 

the switch 

(ACB) 

must be in 

OFF 

position. 

 

P/F 

- Power Factor

. This adjustment is done when the generator is already in parallel with another or others. 

To adjusting the P/F trimmer proceed as follows:

 

 

 

We start by placing the trimmer to the middle position. 

If turning it anti-clockwise, the amperes of generator build-up in relation to the other generator. 

If the trimmer is moved in a clockwise manner, the amperes are reduced in relation to the other or others generators

 

 

GREEN LED CABLE CHECKER. 

The green led will help to achieve the right installation. 

 

The green led (which is located behind the 

VOLT 

trimmer), will help to achieve the right installation. 

It will light 

only*

 if all the below are ok: 

 

1.  

The circuit of this led will activated, if only if a current transformer is installed. 

2.  

The generator is 20% at least under load.  

3.

  The identity of the phases is ok. 

4.

  The suggestion of the phases is ok.  

5.

  The polarity of current transformer is ok. 

   *If there is more than one wrong cable connection at the same time, there is a chance that the green led will be lighten. 

ONE TURN TRIMMER 

THE CLOCKWISE 

TURNING OF STAB 

ADDING STABILITY BUT 

THE GEN HAS SLOWER 

VOLTAGE RECOVERY. 

THE ANTI-CLOCKWISE 

TURNING OF STAB 

DECREASE STABILITY BUT 

THE GEN HAS FASTER 

VOLTAGE RECOVERY. 

(

PRE-ADJUSTED 

TO THE POSITION YOU SEE HERE) 

STABILITY

 

25 TURN TRIMMER (IT DOES NOT STOP) 

UNDER FREQ PROTECTION

 

(DEFAULT 

(PRE-ADJUSTED) 

VALUE: 40 Hz 

THE CLOCKWISE TURNING 

OF UNDER FREQ TRIMMER 

ACTIVATES THIS FEATURE 

AT LOWER Hz. 

(~22Hz THE LOWEST) 

THE ANTI-CLOCKWISE 

TURNING OF UNDER FREQ 

TRIMMER ACTIVATES THIS 

FEATURE AT HIGHER Hz. 

(~74Hz THE HIGHEST) 

 