COMMISSIONING
4.
COMMISSIONING
The Ethernet/IP expansion board allows configuring the SD750 drive as an Ethernet/IP industrial
communication slave. Once loaded the EDS
1
in the Ethernet/IP master, the objects to monitor must be
configured.
NOTICE
Consult implemented objects and their attributes in section
The following steps must be followed:
1. Connect the expansion board and ensure communication with the SD750 is correct (G23).
Configure action in case of communication fault.
2. Load EDS file in the PLC master.
3. Configure network parameters (G21) so they match with the data expected by the master.
4. Configure in the master the objects to exchange between master and slave. In case object Custom
Modbus is used, configure variables in groups G21.3.2 and G21.3.3.
5. Verify communication is stablished. Configure action in case of communication faults with the
master.
6. Configure control parameters G21.3.4 - G21.3.6 based on the application.
The rest of the commissioning depends on the PLC, the program used, etc.
1
Electronic Data Sheet. It is the file that defines a device.