POWER ELECTRONICS
SD750
ETHERNET/IP PROTOCOL
15
EN
EN
Instance
Bit
Byte
7
6
5
4
3
2
1
0
4
Actual Torque (Low Byte)
5
Actual Torque (High Byte)
23
0
NetRef
NetCtrl
Fault Reset Run Rev
Run Fwd
1
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
4
Actual Torque (Low Byte)
5
Actual Torque (High Byte)
24
0
Fault Reset
Run Fwd
1
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
4
Actual Torque (Low Byte)
5
Actual Torque (High Byte)
25
0
At Ref
Ref from
Net
Ctrl from
Net
Running 1
(Fwd)
Warning
Faulted
1
Mode
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
4
Process Reference (Low Byte)
5
Process Reference (High Byte)
70
0
Running 1
(Fwd)
Faulted
1
2
Actual Speed (Low Byte)
–
RPM
3
Actual Speed (High Byte)
–
RPM
71
0
At Ref
Ref from
Net
Ctrl from
Net
Ready
Running 2
(Rev)
Running 1
(Fwd)
Warning
Faulted
1
Drive Status
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
72
0
Running 1
(Fwd)
Faulted
1
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
4
Actual Torque (Low Byte)
5
Actual Torque (High Byte)
73
0
At Ref
Ref from
Net
Ctrl from
Net
Ready
Running 2
(Rev)
Running 1
(Fwd)
Warning
Faulted
1
Drive state
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
4
Actual Torque (Low Byte)
5
Actual Torque (High Byte)
74
0
Running 1
(Fwd)
Faulted
1
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
4
Actual Torque (Low Byte)
5
Actual Torque (High Byte)