4.3.
Configuration and Set up.
4.3.1.
Profipower SD700 Type 1 Module
For this module it can be defined up to 10 Scenarios, 5 for the write
command and the other 5 for the read command. This module is
specific for the SD700 drive, therefore, the Profibus board will be set
up with the valid Modbus address for the SD700. User only must
select the available Modbus registers.
The defined frames for this module are: 10 bytes of Data-Output and
10 bytes of Data-Input.
Therefore, the maximum number of selected Modbus registers will
be 5 for the writing Scenarios and 5 for the reading Scenarios. That
is, all the registers selected for the configured writing Scenarios do
not exceed 5. And in the same way, all the registers selected for the
configured reading Scenarios do not exceed 5.
The description of the Profibus frame will be determined by the
realized set up of the scenarios.