![Powell BriteSpot Plus Instruction Bulletin Download Page 63](http://html1.mh-extra.com/html/powell/britespot-plus/britespot-plus_instruction-bulletin_1585634063.webp)
Powered by Safety
®
53
Appendix D
01.4IB.48041
Appendix D MODBUS Memory Map
Table AB MODBUS Memory Map
Register Name
Read /
Write
Register
Type
Description
Default
Range,
format:
UOM
Register #
Modbus
Offset #
Interpretation
General Parameters - 30000 to 30024
System Configuration
System Serial No. LSW
R
Input
LSW of Unit Serial Number
N/A
0 - 65535
N/A
30000
1
System Serial No. MSW
R
Input
MSW of Unit Serial Number
N/A
0 - 65535
N/A
30001
2
System Manufacture Day/Month
R
Input
High byte in Month, Low byte is Day
N/A
0 - 65535
N/A
30002
3
0x0412 -> April 18th
System Manufacture Year
R
Input
Year since 2000
N/A
0 - 65535
N/A
30003
4
17 -> 2017
HW P/N
R
Input
HW Part Number
10233
0 - 65535
N/A
30004
5
FW Rev
R
Input
CPU FW Revision
N/A
0 - 65535
N/A
30005
6
Comms Card Manufacture Day/Month
R
Input
High byte is Month, Low byte is Day
N/A
0 - 65535
N/A
30006
7
0x0412 -> April 18th
Comms Card Manufacture Year
R
Input
Year since 2000
N/A
0 - 65535
N/A
30007
8
17 -> 2017
Comms Card HW P/N
R
Input
Comms Card Part Number
10235
0 - 65535
N/A
30008
9
Comms Card FW Rev
R
Input
Comms Card FW Revision
N/A
0 - 65535
N/A
30009
10
Power Card Manufacture Day/Month
R
Input
High byte is Month, Low byte is Day
N/A
0 - 65535
N/A
30010
11
Power Card Manufacture Year
R
Input
Year since 2000
N/A
0 - 65535
N/A
30011
12
Power Card HW P/N
R
Input
Power Card Part Number
10234
0 - 65535
N/A
30012
13
Power Card FW Rev
R
Input
Power Card FW Revision
N/A
0 - 65535
N/A
30013
14
Expansion Card Manufacture Day/Month
R
Input
High byte is Month, Low byte is Day
0
0 - 65535
N/A
30014
15
Expansion Card Manufacture Year
R
Input
Year since 2000
0
0 - 65535
N/A
30015
16
Expansion Card HW P/N
R
Input
Expansion Card Part Number
0
0 - 65535
N/A
30016
17
Expansion Card FW Rev
R
Input
Expansion Card FW Revision
0
0 - 65535
N/A
30017
18
System Time
Year
R
Input
Device Years from RTC
N/A
2000 - 2099
N/A
30018
19
Month
R
Input
Device Months from RTC
N/A
1 - 12
N/A
30019
20
Day
R
Input
Device Days from RTC
N/A
1 - 31
N/A
30020
21
Hour
R
Input
Device Hours from RTC
N/A
0 - 23
N/A
30021
22
Min
R
Input
Device Minutes from RTC
N/A
0 - 59
N/A
30022
23
Sec
R
Input
Device Seconds from RTC
N/A
0 - 59
N/A
30023
24
Board Parameters
Mem Capacity
R
Input
Amount of Storage Memory Used
N/A
0 - 100
%
30024
25
Degree CF
R
Input
Degree C or F Flag (1 = C, 2 = F)
1
1 - 2
N/A
30025
26
(1 = C, 2 = F)
Log Time
R
Input
Log Interval (minutes)
5
0 - 1440
Minutes
30026
27
Overview Status - 30040 to 30042
Alarm Status
R
Input
Bit-mask status of all alarms 1 = Activated
N/A
0 - 255
N/A
30040
41
0x0004 -> Alarm 3 in Alarm condition.
Warning Status
R
Input
Bit-mask status of all warnings 1 = Activated
N/A
0 - 255
N/A
30041
42
0x0082 -> Alarm 8 and 2 in Warning condition.
Relay Status
R
Input
Bit-mask status of all relays 1 = Activated
N/A
0 - 7
N/A
30042
43
0x0001 -> Relay 1 activated.
Relay Status - 30050 to 30053
All Condition
R
Input
Bit-mask condition of all relays. 0 = Warning, 1 = Alarm.
N/A
0 - 7
N/A
30050
51
Relay 1 Inputs
R
Input
Bit-mask of alarm sources for Relay 1
N/A
0 - 255
N/A
30051
52
Relay 2 Inputs
R
Input
Bit-mask of alarm sources for Relay 2
N/A
0 - 255
N/A
30052
53
Relay 3 Inputs
R
Input
Bit-mask of alarm sources for Relay 3
N/A
0 - 255
N/A
30053
54
Summary of Contents for BriteSpot Plus
Page 4: ...Powered by Safety 01 4IB 48041 BriteSpot Plus This page is left blank intentionally ...
Page 29: ...Powered by Safety 19 Installation 01 4IB 48041 Figure 20 Panel Mount Clip Installation X X ...