9
Equipment Description
01.4IB.48041
Table B System Specifications (cont.)
Characteristic
Minimum
Typical
Maximum
Units
Comments
Operating Environmental Conditions
Temperature
-30 (-22)
70 (158)
oC (oF)
IEC 60068-2-14
Note: LCD viewing angle is reduced when ambient temperatures are below -20 oC
Humidity
5
95
%RH
Non-condensing
IP Rating (Mounted)
54
IEC 60529:2009
Vibration
Class 1
IEC 60255-21-1
Shock
Class 1
IEC 60255-21-2
Pollution Degree
2
Overvoltage Category
II
Altitude
2000
MASL
(meters above
sea level)
Atmospheric Pressure
80
110
kPa
(kilopascal)
Storage Environmental Conditions
Temperature
-40 (-40)
85 (185)
oC (oF)
Humidity
5
95
%RH
Vibration
Class 1
IEC 60255-21-1
Shock
Class 1
IEC 60255-21-2
Bump
Class 1
IEC 60255-21-3
Standard Probe Specifications (BSL007, BSL010, BSL015)
Material
Nylon
Minimum Bend Radius
12 (0.5)
mm (in)
Length
7, 10, 15, (21, 30, 45)
m (ft)
Operating Temperature
-40 (-40)
120 (248)
oC (oF)
High Voltage Characteristics
38kV, over 8” gap
High Temperature Probe Specifications (BSPN/AHT)
Material
Fluoropolymer
Minimum Bend Radius
12 (0.5)
mm (in)
Length
Detachable probe, 0.25m (10”). Max fiber extension 10m (30’)
Operating Temperature
-40 (-40)
160 (320)
oC (oF)
High Voltage Characteristics
38kV, over 8” gap
Probe Mounting Fixture Specifications
Material
Tin plated copper
Manufacturer
Tyco/Amp
Approvals
UL/CSA
Part Numbers
¼” Hardware
Tyco/Amp PN 33465
3/8” Hardware
Tyco/Amp PN 36807
½” Hardware
Tyco/Amp PN 36808