Part No. 5106463
39
Fig. 28
Replacement of Thermostats
(Flowsure/F)
1. Remove the front and top covers.
2. Pull off the temperature control knob.
3. Un-clip the programmer assembly and push into the
controls assembly.
4. Remove the facia retaining screws at the base of the
facia.
5. Lift off the facia and disconnect the indicator lights
plug.
6. Disconnect the inside and rear electrical connectors.
7. Remove the controls assembly lid securing screws
and remove the lid.
Note which way the electrical connectors fit before
removing any of the thermostats.
Re-assemble in reverse order unless stated otherwise.
Boiler Control Thermostat
1. Disconnect the electrical connections.
2. Remove the clip and withdraw the sensor from its
pocket.
3. Remove the locknut securing the thermostat spindle
to the controls assembly.
Limit Thermostat
1. Disconnect the electrical connections.
2. Remove the clip and withdraw the temperature
gauge bulb and limit thermostat sensor
from its pocket.
3. Remove the locknut securing the thermostat to the
controls assembly. On re-assembly insert
the thermostat sensor before the temperature
gauge bulb.
Pump Overrun Thermostat
1. Disconnect the electrical connections.
2. Unscrew the two screws securing the thermostat
to the controls assembly.
3. Remove the clip and withdraw the sensor from its
pocket.
Tank Limit Thermostat (F)
1. Disconnect the electrical connections.
2. Unscrew the two screws securing the thermostat
to the controls assembly.
3. Remove the clip and withdraw the sensor from
its pocket.
DHW Overheat Thermostat (Flowsure)
1. Disconnect the electrical connections.
2. Unscrew the two screws securing the
thermostat to the controls assembly.
3. Remove the clip and withdraw the sensor
from its pocket.
Heatstore Thermostat (F)
1. Disconnect the electrical connections.
2. Unscrew the two screws securing the
thermostat to the bracket on the pipe.
Automatic Air Vent
1. Drain the boiler using the boiler drain point
provided.
2. Unscrew the automatic air vent and fit a
new one in the reverse order.
3. Fill the system as described in Section 2-
Pre - installation Requirements.
Servicing & Maintenance