Part No. 5106463
19
Where the terminal is within 1 metre of any
plastic material, such material should be
protected from the effects of combustion
products.
There are additional general requirements
in most Regulations and Standards that the
flue must be positioned so that it does not
cause a nuisance and permits the dispersal
of combustion products.
If the terminal is less than 2 metres above
ground level, balcony or place to which any
person has access, the terminal must be
protected by a guard, (Flue Guard Part No.
26000045).
Table 3
Fig. 13
600
600
75
600
300
300
300
600
1200
1500
750
300
1000
Terminal Position with Minimum Distance (mm)
L
G
G
E
D
K
G
A
A
D
F
H,J
C
F
Likely flue positions requiring
a flue terminal guard
B
N
N
M
N
M
FLU0003A
Property
Boundary
Line
Terminal
Assembly
300 min
Top
View
Pressure Jet
Appliance
FLU0004A
A
Directly below an opening, air brick, opening window
etc
B
Horizontally to an opening, air brick, opening window
etc
C
Below a plastic/painted gutter, drainage pipe or eaves,
with protection
D
Below a balcony or a plastic/painted gutter, drainage
pipe or eaves
E
From vertical sanitary pipework
F
From an internal or external corner
G
Above ground or balcony level
H
From a surface facing a terminal
J
From a terminal facing the terminal
K
Vertically from a terminal on the same wall
L
Horizontally from a terminal on the same wall
M
From the intersection with the roof to the air intake on
the terminal
N
From the terminal to a wall or chimney
Clearances Required Around Balanced and Low Level Discharge Flues Fitted to Oil Fired Boilers
Pre-Installation Requirements
Note: The distance from a appliance terminal installed parallel to a
boundary may not be less than 300 mm in accordance with the diagram
below.