25
9.0 Installation
© Baxi Heating UK Ltd 2016
9.4
Fitting The Boiler
1. Remove the sealing caps from the boiler connections.
NOTE:
A small amount of water may drain from the boiler
once the caps are removed.
2. Lift the boiler as indicated by the shaded areas. The boiler
should be lifted by TWO PEOPLE. Engage the mounting
bracket at the top rear of the boiler on the wall plate (Fig. 21)
(see
Safe Manual Handling
page 5).
3.
Insert the sealing washers between the valves and pipes on
the wall plate and the boiler connections. Tighten all the
connections.
9.5
Fitting the Safety Pressure Relief Discharge
Pipe (Fig. 22)
1. Remove the discharge pipe from the kit.
2. Determine the routing of the discharge pipe in the vicinity of
the boiler. Make up as much of the pipework as is practical,
including the discharge pipe supplied.
IMPORTANT:
Make all soldered joints before connecting
to the pressure relief valve. The relief valve is intentionally
angled to the right of the boiler. DO NOT adjust the
position of the valve. The discharge pipe must be installed
before pressurising the system.
3. The pipework must be at least 15mm diameter and run
continuously downwards to a discharge point outside the
building. See section 6.7 for further details.
4. Utilising one of the sealing washers, connect the discharge
pipe to the adaptor and tighten the nut hand tight, plus 1/4
turn to seal.
5. Complete the discharge pipework and route it to the
outside discharge point.
9.6
Condensate Drain
(see section 7.7)
(Fig. 23)
1. Using the short piece of rubber hose supplied, connect the
condensate drain pipework to the boiler condensate trap
outlet pipe. When connecting the hose, ensure that the
condensate sump is not inadvertently unscrewed,
Ensure the discharge of condensate complies with any
national or local regulations in force (see British Gas
“Guidance Notes for the Installation of Domestic Gas
Condensing Boilers” & HHIC recommendations).
2. The hose will accept 21.5mm (
3
/
4
in) plastic overflow pipe
which should generally discharge internally into the household
drainage system. If this is not possible, discharge into an outside
drain is acceptable.
3. The boiler condensate trap should be primed by pouring
approximately 300ml of water into the flue spigot (Fig. 22a).
Do not allow any water to fall into the air inlet.
Fig. 22
Pressure Relief Valve
Discharge Pipe
Fig. 21
Suggested Lifting Points
shown as shaded area
Condensate Trap
Outlet Connection
Remove Sealing Caps from
under the Boiler before lifting
into position
Sealing Washers
Control Box removed
for clarity
Fig. 23
Boiler Mounting
Bracket
Prime Trap by pouring
300ml of water into
flue spigot
Rubber Hose
Fig. 22a