22
8.0 Flue Options
© Baxi Heating UK Ltd 2016
8.2
Flue Lengths
The standard horizontal telescopic flue kit allows for lengths
between 315mm and 500mm from elbow to terminal without the
need for cutting (Fig. 14).
Extensions of 250mm, 500mm & 1m are available.
The maximum permissible equivalent flue length is:
10 metres (60/100 system - vertical & horizontal)
20 metres (80/125 system - vertical & horizontal)
15 metres (80/80 twin pipe)
8 metres (60/100 system - vertical connected
to ridge terminal)
8.3
Flue Trim
1. The flexible flue trims supplied can be fitted on the outer and
inner faces of the wall of installation.
8.4
Terminal Guard (Fig. 15)
1. When codes of practice dictate the use of terminal guards
‘Multifit’ accessory part no. 720627901 can be used (Note: This is
not compatible with Flue Deflector referred to below).
2. There must be a clearance of at least 50mm between any part
of the terminal and the guard.
3. When ordering a terminal guard, quote the appliance name and
model number.
4. The flue terminal guard should be positioned centrally over the
terminal and fixed as illustrated.
8.5
Flue Deflector (Fig. 16)
1. Push the flue deflector over the terminal end. It may point
upwards as shown, or up to 45° either way from vertical. Secure
the deflector to the terminal with screws provided.
8.6
Flue Accessories
1. For full details of Flue Accessories (elbows, extensions, clamps
etc.) refer to the Flue Installation Guide supplied in the literature
pack.
Fig. 15
Fig. 16
315mm
500mm
Flue Deflector
Fig. 14
Ensure that no part of the
white outer chimney duct
is visible