background image

4

 INSTALLATION – GENERAL     

 

      

 (SEE FIGS. 2 - 6)

PIPE FITTINGS

 

All pipe fittings are made via 22mm compression 

fittings directly to the unit. The fittings are  threaded 

3/4”BSP male parallel should threaded pipe connec-

tions be required.

  

COLD FEED

A 22mm cold water supply is recommended, how-

ever, if a 15mm (1/2”) supply exists, which provides 

sufficient flow, this may be used (although more flow 

noise may be experienced). 

A stopcock or servicing valve should be incorporated 

into the cold water supply to enable the POTTERTON 

GOLD  cylinder  and  its  associated  controls  to  be 

isolated and serviced.

COLD WATER COMBINATION VALVE ASSEMBLY (FIG. 

2)

The 2-piece cold water combination valve assembly 

can be located anywhere on the cold water mains 

supply prior to the expansion vessel ( see Fig. 6 Page 

9 ) but the two pieces do not have to be installed 

together.

Fig. 2: Cold water combination valve assembly

DRAIN TAP

A suitable draining tap should be installed in the cold 

water supply to the POTTERTON GOLD cylinder

between the expansion valve ( see Fig. 6 Page 9 ) 

and the heater at as low a level as possible. It is 

recommended that the outlet point of the drain 

pipework be at least 1 metre below the level of the 

heater (this can be achieved by attaching a hose to 

the drain tap outlet spigot).

EXPANSION VESSEL

The  expansion  vessel  accommodates  expansion 

that results from heating the water inside the unit. 

The expansion vessel is pre-charged at 3.5 bar. The 

expansion vessel must be connected  between the 

expansion valve (see Fig. 2) and the POTTERTON 

GOLD cylinder 

( see Fig. 6 Page 9 ).

 The location of the 

expansion vessel should allow access to recharge the 

pressure as and when necessary, this can be done 

using a normal car foot pump. It is recommended 

that the expansion vessel is adequately supported.  

An  expansion  vessel  wall  mounting  bracket  is 

supplied for this purpose and should be fitted.

OPERATIONAL SUMMARY

Maximum mains pressure 

 

16 bar

Operating pressure   

 

3.5 bar

Expansion vessel charge pressure 

3.5 bar

Expansion relief valve setting    

6 bar

T&P relief valve setting  

                   90°C/10 bar

Maximum primary circuit pressure 

3 bar

(indirect only)

Storage capacity 

 

 

See Table1

Weight when full 

 

 

See Table1

LIMITATIONS

The POTTERTON GOLD cylinder should not be used 

in association with any of the following:

• 

Solid fuel boilers or any other boiler in which

        the energy input is not under effective

        thermostatic control, unless additional and

        appropriate safety measures are installed.

• 

Ascending spray type bidets or any other

  

class 1 back syphonage risk requiring that a type 

        A air gap be employed.

• 

Steam heating plants unless additional and  

 

appropriate safety devices are installed.

• 

Situations where maintenance is likely to be

        neglected or safety devices tampered with.

• 

Water supplies that have either inadequate  

 

pressure or where the supply may be intermittent.

• 

Situations where it is not possible to safely 

        pipe away any discharge from the safety valves.

•       In areas where the water consistently contains a

         high proportion of solids, e.g. suspended matter

 that could block the strainer,  unless adequate  

filtration can be ensured.  

                                                                  

The  pressure  reducing  valve  incorporates  the 

pressure reducer and strainer and the expansion valve 

incorporates the expansion and check valves. Ensure 

that the valves are installed in the correct order 

and orientation. No other valves should be placed 

between the expansion valve and the POTTERTON 

GOLD cylinder. A connection can be made between 

the  expansion  and  pressure  reducing  valves  to 

provide  a  balanced  cold  water  connection. The 

expansion valve connection must not be used for 

any other purpose.

SECONDARY CIRCULATION

If secondary circulation is required it is recommended 

that  it  be  connected  to  the  POTTERTON  GOLD 

cylinder as shown

 in Fig. 3 v

ia a swept tee joint into 

the cold feed to the unit. A swept tee joint is available 

as an accessory (order code no. 5133565).

The secondary return pipe should be in 15mm pipe 

and incorporate a check valve to prevent backflow. 

A suitable WRAS approved bronze circulation pump 

will be required. On large systems, due to the

Summary of Contents for Gold H Range

Page 1: ...he unit should be stored in an upright position in an area free from excessive damp or humidity This appliance complies with the requirements of the CE marking directive and is Kiwa approved to show compliance with Building Regulations Section G3 The following instructions are offered as a guide to installation which must be carried out by a competent plumbing and electrical installer in accordanc...

Page 2: ...LLATION GENERAL 4 INSTALLATION 10 COMMISSIONING 13 MAINTENANCE 14 USER INSTRUCTIONS 15 FAULT FINDING AND SERVICING 16 HEAT LOSS 18 ENVIRONMENTAL INFORMATION 18 COMMISSIONING CHECK LIST 19 SERVICE RECORD 20 GUARANTEE 21 TECHNICAL SUPPORT AND SPARES 24 PAGE ...

Page 3: ...t these values outlet flow rates may be poor if several outlets are used simultaneously Thehighertheavailablepressure and flow rate the better the system performance The POTTERTON GOLD cylinder has an operating pressure of 3 5 bar which is controlled by the cold water combination valve assembly The cold water combination valve assembly can be connected to a maximum mains pressure of 16 bar OUTLET ...

Page 4: ...re 3 5 bar Expansion vessel charge pressure 3 5 bar Expansion relief valve setting 6 bar T P relief valve setting 90 C 10 bar Maximum primary circuit pressure 3 bar indirect only Storage capacity See Table1 Weight when full See Table1 LIMITATIONS The POTTERTON GOLD cylinder should not be used in association with any of the following Solid fuel boilers or any other boiler in which the energy input ...

Page 5: ...of 15mm pipe to terminal fittings such as sinks and basins Pipe sizes may vary due to system design increaseinsystemwatercontent itmaybenecessary tofitanadditionalexpansionvesseltothesecondary circuit This should be done if the capacity of the secondary circuit exceeds 10 litres Pipe capacity copper 15mm O D 0 13 l m 10 litres 77m 22mm O D 0 38 l m 10 litres 26m 28mm O D 0 55 l m 10 litres 18m ...

Page 6: ...NAL CAPACITY litres A B C D RATING kW RECOVERY mins HEATING TIME DIRECT mins 100 120 120 150 315 364 615 906 364 800 1090 315 364 925 1216 364 1184 1474 12 5 23 89 100 364 493 784 89 110 110 142 142 163 1731 2045 1378 1693 364 364 315 150 170 HEAT UP TIME mins 27 210 210 250 250 364 615 906 315 364 800 1090 364 925 1216 315 364 1184 1474 12 5 24 16 0 29 205 170 315 364 493 784 11 2 20 163 205 252 ...

Page 7: ...e than 600mm of pipe between the valve outlet and the tundish see Diagram 1 Note To comply with the Water Supply Water Fittings Regulations the tundish should incorporate a suitable air gap 3 55 Any discharge should be visible at the tundish In addition where discharges from safety devices may not be apparent e g in dwellings occupied by people with impaired vision or mobility consideration should...

Page 8: ...a discharge pipe D2 having 4 No elbows and length of 7m from the tundish to the point of discharge From Table 3 Maximum resistance allowed for a straight length of 22mm copper discharge pipe D2 from a G1 2 temperature relief valve is 9 0m Subtract the resistance for 4 No 22mm elbows at 0 8m each 3 2m Therefore the permitted length equates to 5 8m 5 8m is less than the actual length of 7m therefore...

Page 9: ... and worked example 300mm minimum 600mm maximum Metal discharge pipe D1 from Temperature relief valve to tundish Tundish Safety device e g Temperature relief valve Fig 6 Typical installation schematic EXPANSION VESSEL T P RELIEF VALVE TO HOT OUTLETS MAINS WATER SUPPLY ISOLATING VALVE NOT SUPPLIED TUNDISH DISCHARGE PIPE DRAIN COCK NOT SUPPLIED PRIMARY RETURN PRIMARY FLOW ELEMENT CONTROLS HOUSING IN...

Page 10: ...0730 The POTTERTON GOLD MUST be earthed Allwiringtotheunitmustbeinstalledin accordance with the latest IEEWiring Regulations and the circuit must be protected by a suitable fuse and double pole isolating switch with a contact separation of at least 3mm in both poles The live and neutral connections are made directly onto the combined thermostat and thermal cut out located under the terminal cover ...

Page 11: ...ing bulbs are pushed fully into the pockets on the element plate assembly BOILER SELECTION Theboilershouldhaveacontrolthermostatandnon self resetting thermal cut out and be compatible with unvented storage water heaters Where use of a boiler without a thermal cut out is unavoidable a low head open vented primary circuit should be used The feed and expansion cistern head above the POTTERTON GOLD cy...

Page 12: ...12 Fig 8 Schematic wiring diagram Basic 2 x 2 port valve system Fig 9 Schematic wiring diagram 3 port mid position valve system N B Must be used in conjunction with 2 port zone valve supplied ...

Page 13: ...emperature can be adjusted by inserting a flat bladedscrewdriverintheadjustmentknobontopof the immersion heater thermostat and rotating The adjustment range 1 to 5 represents a temperature range of 10o to 70o C Check the operation of thermostat s and that no water has issued from the expansion relief valve or temperature pressure relief valve during the heating cycle Fig 10 Indirect thermostat and...

Page 14: ...0o to 70o C Check the operation of thermostat s and that no water has issued from the expansion relief valve or temperature pressure relief valve during the heating cycle INDIRECT UNITS Openthecover s totheimmersionheaterhousing s and disconnect wiring from immersion heater s thermostat s Removethermostatbycarefullypulling outwards Removethermostatcapillarysensorsfrom the pockets on the immersion ...

Page 15: ...S IMMER SION HEATER S A combined adjustable thermostat and thermal cut out is provided for each immersion heater The thermostat is factory set to give a water storage temperature of approx 55o to 60o C Access to the thermostat can be made by opening the immer sion heater cover DISCONNECT THE ELECTRICAL SUPPLY BEFORE OPENING THE COVER S Tempera ture adjustment is made by inserting a flat bladed scr...

Page 16: ...equipment covers NEVER bypass any thermal controls or operate system without the necessary safety valves Water contained in the POTTERTON GOLD cylinder may be very hot especially following a thermal control failure Caution must be taken when drawing water from the unit SPARE PARTS A full range of spare parts are available for the POTTERTON GOLD cylinder range SeeTable 4 Page 17 Refer to the techni...

Page 17: ...e ra ture Pre ssure R e lie f Va lv e 95 6 0 5 8 10 Ex pa nsio n v e sse l 1 2 litre 1 0 0 12 0 a nd 1 5 0 litre mo de ls 95 6 0 7 8 63 Ex pa nsio n v e sse l 1 8 litre 1 7 0 a nd 2 1 0 litre mo de ls 95 6 0 7 8 64 Ex pa nsio n v e sse l 2 4 litre 2 5 0 a nd 3 0 0 litre mo de ls 95 6 0 7 6 12 C o mbine d the rmo sta t a nd the rma l cut o ut 95 6 1 2 0 26 Te rmina l co v e r 95 6 1 4 0 94 A cce ss...

Page 18: ...e 4 INDIRE CT boiler not work ing 4 Chec k boiler operation If fault is s us pec ted c ons ult boiler m anufac turer s ins truc tions 5 INDIRE CT therm al c ut out has operated 5 Chec k Res et by pus hing button on c ut out Fig 10 Page 13 Chec k operation of indirec t therm os tat 6 INDIRE CT m otoris ed valve not c onnec ted c orrec tly 6 Chec k wiring and or plum bing connections to m otoris ed ...

Page 19: ...19 ...

Page 20: ...20 ...

Page 21: ...e of installation The Benchmark Checklist has been completed upon commissioning and the Benchmark Service Record is completed for each service It has not been modified in any way other than by POTTERTON GOLD It has not been frost damaged It has only been used for the storage of potable water It has not been tampered with or been subjected to misuse or neglect The fault is not scale related Within6...

Page 22: ...22 NOTES ...

Page 23: ...23 NOTES ...

Page 24: ... we reserve the right to change specifications and guarantee terms and conditions without notice For all technical support and replacement parts issues please contact POTTERTON GOLD Brooks House Coventry Road Warwick CV34 4LL Tel 0844 871 1532 36006077 Issue 04 TECHNICAL SUPPORT SPARES ...

Reviews: