Potterton Gold H Range Installation And Servicing Instructions Download Page 14

14

 

MAINTENANCE

MAINTENANCE REQUIREMENTS

Unvented  hot  water  systems  have  a  continuing 

maintenance requirement in order to ensure safe 

working and optimum performance. It is essential 

that the relief valve(s) are periodically inspected and 

manually opened to ensure no blockage has

occurred in the valves or discharge pipework.

Similarly cleaning of the strainer element and

replacement of the air in the expansion vessel will 

help to prevent possible operational faults.

The maintenance checks described below should be 

performed by a competent person on a regular basis, 

e.g. annually to coincide with boiler maintenance.

After  any  maintenance,  please  complete  the 

relevant  Service  Interval  Record  section  of  the 

Benchmark Checklist located on Page 19 and 20 of 

this document.

SAFETY VALVE OPERATION

Manually operate the temperature/pressure relief 

valve for a few seconds. Check water is discharged 

and that it flows freely through the tundish and 

discharge pipework. Check valve reseats correctly 

when released. 

NOTE: Water discharged may be 

very hot!

Repeat  the  above  procedure  for  the  Expansion 

Valve.

STRAINER

Turn off the cold water supply, boiler and immersion 

heaters. The lowest hot water tap should then be 

opened to de-pressurise the system. Remove the 

pressure reducing cartridge to access the strainer 

mesh. Wash any particulate matter from the strainer 

under clean water. Re-assemble ensuring the seal 

is correctly fitted. DO NOT use any other type of 

sealant.

DESCALING IMMERSION HEATER(S)

Before removing the immersion heater(s) the unit 

must be drained. 

Ensure the water, electrical supply 

and  boiler  are  OFF  before  draining.

  Attach  a 

hosepipe to the drain cock having sufficient length 

to take water to a suitable discharge point below the 

level of the  unit. Open a hot tap close to the unit 

and open drain cock to drain unit.

DIRECT UNITS

Switch  on  electrical  supply  to  the  immersion 

heater(s) and allow the Potterton Gold to heat up to 

normal working temperature (60ºC recommended, 

approximately graduation 4 on the thermostat). If 

necessary the temperature can be adjusted by in-

serting a flat bladed screwdriver in the adjustment 

knob on top of the immersion heater thermostat 

and rotating. 

The adjustment range 1 to 5 represents a tempera-

ture range of 10

o

 to 70

o

C. Check the operation of  

thermostat(s) and that no water has issued from 

the expansion relief valve or temperature/pressure 

relief valve during the heating cycle.

IN

DIRECT UNITS

Open the cover(s) to the immersion heater housing(s) 

and disconnect wiring from immersion heater(s) 

thermostat(s). Remove thermostat by carefully pulling 

outwards. Remove thermostat capillary sensors from 

the pockets on the immersion heater. Unscrew

immersion heater backnut(s) and remove immersion 

heater from the unit.  A key spanner is supplied 

with the POTTERTON GOLD cylinder unit for easy 

removal/tightening  of  the  immersion  heater(s). 

Over time the immersion heater gasket may become 

stuck to the mating surface. To break the seal insert 

a round bladed screwdriver into one of the pockets 

on the immersion heater and gently lever up and 

down.

 

Carefully remove any scale from the surface of the 

element(s). DO NOT use a sharp implement as

damage to the element surface could be caused. 

Ensure sealing surfaces are clean and seals are

undamaged, if in doubt fit a new gasket

(part number 95 611 822).

 

        Replace immersion heater(s) ensuring the lower

(right angled) element hangs vertically downwards 

towards the base of the unit. It may be helpful to 

support the immersion heater using a round bladed 

screwdriver  inserted  into  one  of  the  thermostat 

pockets whilst the backnut is tightened. Replace 

thermostat  capillaries  into  pocket.  Replace  the 

immersion heater thermostat by carefully plugging 

the two male spade terminations on the underside 

of  the  thermostat  head  into  the  corresponding 

terminations on the element. Rewire, check, close 

and secure immersion heater housing cover(s).

 

 

EXPANSION VESSEL CHARGE PRESSURE

Remove the dust cap on top of the vessel. Check the 

charge pressure using a tyre pressur

e gauge. The 

pressure (with system de-pressurised) should be 3.5 bar. 

If it is lower than the required setting it should be 

re-charged using a tyre pump (Schrader valve type). 

DO NOT OVER-CHARGE. Re-check the pressure and 

when correct replace the dust cap.

RE-COMMISSIONING

 

Check all electrical and plumbing connections are 

secure. Close the drain cock. With a hot tap open, 

turn on the cold water supply and allow unit to 

refill. 

DO NOT

 switch on the immersion heater(s) or 

boiler until the unit is full. When water flows from 

the hot tap allow to flow for a short while to purge 

air and flush through any disturbed particles. Close 

hot tap and then open successive hot taps in system 

to purge any air.

 

Summary of Contents for Gold H Range

Page 1: ...he unit should be stored in an upright position in an area free from excessive damp or humidity This appliance complies with the requirements of the CE marking directive and is Kiwa approved to show compliance with Building Regulations Section G3 The following instructions are offered as a guide to installation which must be carried out by a competent plumbing and electrical installer in accordanc...

Page 2: ...LLATION GENERAL 4 INSTALLATION 10 COMMISSIONING 13 MAINTENANCE 14 USER INSTRUCTIONS 15 FAULT FINDING AND SERVICING 16 HEAT LOSS 18 ENVIRONMENTAL INFORMATION 18 COMMISSIONING CHECK LIST 19 SERVICE RECORD 20 GUARANTEE 21 TECHNICAL SUPPORT AND SPARES 24 PAGE ...

Page 3: ...t these values outlet flow rates may be poor if several outlets are used simultaneously Thehighertheavailablepressure and flow rate the better the system performance The POTTERTON GOLD cylinder has an operating pressure of 3 5 bar which is controlled by the cold water combination valve assembly The cold water combination valve assembly can be connected to a maximum mains pressure of 16 bar OUTLET ...

Page 4: ...re 3 5 bar Expansion vessel charge pressure 3 5 bar Expansion relief valve setting 6 bar T P relief valve setting 90 C 10 bar Maximum primary circuit pressure 3 bar indirect only Storage capacity See Table1 Weight when full See Table1 LIMITATIONS The POTTERTON GOLD cylinder should not be used in association with any of the following Solid fuel boilers or any other boiler in which the energy input ...

Page 5: ...of 15mm pipe to terminal fittings such as sinks and basins Pipe sizes may vary due to system design increaseinsystemwatercontent itmaybenecessary tofitanadditionalexpansionvesseltothesecondary circuit This should be done if the capacity of the secondary circuit exceeds 10 litres Pipe capacity copper 15mm O D 0 13 l m 10 litres 77m 22mm O D 0 38 l m 10 litres 26m 28mm O D 0 55 l m 10 litres 18m ...

Page 6: ...NAL CAPACITY litres A B C D RATING kW RECOVERY mins HEATING TIME DIRECT mins 100 120 120 150 315 364 615 906 364 800 1090 315 364 925 1216 364 1184 1474 12 5 23 89 100 364 493 784 89 110 110 142 142 163 1731 2045 1378 1693 364 364 315 150 170 HEAT UP TIME mins 27 210 210 250 250 364 615 906 315 364 800 1090 364 925 1216 315 364 1184 1474 12 5 24 16 0 29 205 170 315 364 493 784 11 2 20 163 205 252 ...

Page 7: ...e than 600mm of pipe between the valve outlet and the tundish see Diagram 1 Note To comply with the Water Supply Water Fittings Regulations the tundish should incorporate a suitable air gap 3 55 Any discharge should be visible at the tundish In addition where discharges from safety devices may not be apparent e g in dwellings occupied by people with impaired vision or mobility consideration should...

Page 8: ...a discharge pipe D2 having 4 No elbows and length of 7m from the tundish to the point of discharge From Table 3 Maximum resistance allowed for a straight length of 22mm copper discharge pipe D2 from a G1 2 temperature relief valve is 9 0m Subtract the resistance for 4 No 22mm elbows at 0 8m each 3 2m Therefore the permitted length equates to 5 8m 5 8m is less than the actual length of 7m therefore...

Page 9: ... and worked example 300mm minimum 600mm maximum Metal discharge pipe D1 from Temperature relief valve to tundish Tundish Safety device e g Temperature relief valve Fig 6 Typical installation schematic EXPANSION VESSEL T P RELIEF VALVE TO HOT OUTLETS MAINS WATER SUPPLY ISOLATING VALVE NOT SUPPLIED TUNDISH DISCHARGE PIPE DRAIN COCK NOT SUPPLIED PRIMARY RETURN PRIMARY FLOW ELEMENT CONTROLS HOUSING IN...

Page 10: ...0730 The POTTERTON GOLD MUST be earthed Allwiringtotheunitmustbeinstalledin accordance with the latest IEEWiring Regulations and the circuit must be protected by a suitable fuse and double pole isolating switch with a contact separation of at least 3mm in both poles The live and neutral connections are made directly onto the combined thermostat and thermal cut out located under the terminal cover ...

Page 11: ...ing bulbs are pushed fully into the pockets on the element plate assembly BOILER SELECTION Theboilershouldhaveacontrolthermostatandnon self resetting thermal cut out and be compatible with unvented storage water heaters Where use of a boiler without a thermal cut out is unavoidable a low head open vented primary circuit should be used The feed and expansion cistern head above the POTTERTON GOLD cy...

Page 12: ...12 Fig 8 Schematic wiring diagram Basic 2 x 2 port valve system Fig 9 Schematic wiring diagram 3 port mid position valve system N B Must be used in conjunction with 2 port zone valve supplied ...

Page 13: ...emperature can be adjusted by inserting a flat bladedscrewdriverintheadjustmentknobontopof the immersion heater thermostat and rotating The adjustment range 1 to 5 represents a temperature range of 10o to 70o C Check the operation of thermostat s and that no water has issued from the expansion relief valve or temperature pressure relief valve during the heating cycle Fig 10 Indirect thermostat and...

Page 14: ...0o to 70o C Check the operation of thermostat s and that no water has issued from the expansion relief valve or temperature pressure relief valve during the heating cycle INDIRECT UNITS Openthecover s totheimmersionheaterhousing s and disconnect wiring from immersion heater s thermostat s Removethermostatbycarefullypulling outwards Removethermostatcapillarysensorsfrom the pockets on the immersion ...

Page 15: ...S IMMER SION HEATER S A combined adjustable thermostat and thermal cut out is provided for each immersion heater The thermostat is factory set to give a water storage temperature of approx 55o to 60o C Access to the thermostat can be made by opening the immer sion heater cover DISCONNECT THE ELECTRICAL SUPPLY BEFORE OPENING THE COVER S Tempera ture adjustment is made by inserting a flat bladed scr...

Page 16: ...equipment covers NEVER bypass any thermal controls or operate system without the necessary safety valves Water contained in the POTTERTON GOLD cylinder may be very hot especially following a thermal control failure Caution must be taken when drawing water from the unit SPARE PARTS A full range of spare parts are available for the POTTERTON GOLD cylinder range SeeTable 4 Page 17 Refer to the techni...

Page 17: ...e ra ture Pre ssure R e lie f Va lv e 95 6 0 5 8 10 Ex pa nsio n v e sse l 1 2 litre 1 0 0 12 0 a nd 1 5 0 litre mo de ls 95 6 0 7 8 63 Ex pa nsio n v e sse l 1 8 litre 1 7 0 a nd 2 1 0 litre mo de ls 95 6 0 7 8 64 Ex pa nsio n v e sse l 2 4 litre 2 5 0 a nd 3 0 0 litre mo de ls 95 6 0 7 6 12 C o mbine d the rmo sta t a nd the rma l cut o ut 95 6 1 2 0 26 Te rmina l co v e r 95 6 1 4 0 94 A cce ss...

Page 18: ...e 4 INDIRE CT boiler not work ing 4 Chec k boiler operation If fault is s us pec ted c ons ult boiler m anufac turer s ins truc tions 5 INDIRE CT therm al c ut out has operated 5 Chec k Res et by pus hing button on c ut out Fig 10 Page 13 Chec k operation of indirec t therm os tat 6 INDIRE CT m otoris ed valve not c onnec ted c orrec tly 6 Chec k wiring and or plum bing connections to m otoris ed ...

Page 19: ...19 ...

Page 20: ...20 ...

Page 21: ...e of installation The Benchmark Checklist has been completed upon commissioning and the Benchmark Service Record is completed for each service It has not been modified in any way other than by POTTERTON GOLD It has not been frost damaged It has only been used for the storage of potable water It has not been tampered with or been subjected to misuse or neglect The fault is not scale related Within6...

Page 22: ...22 NOTES ...

Page 23: ...23 NOTES ...

Page 24: ... we reserve the right to change specifications and guarantee terms and conditions without notice For all technical support and replacement parts issues please contact POTTERTON GOLD Brooks House Coventry Road Warwick CV34 4LL Tel 0844 871 1532 36006077 Issue 04 TECHNICAL SUPPORT SPARES ...

Reviews: