background image

Page 2

Notice for all UDACT-9000 Sold in Canada:

Potter's 

 UDACT-9000 Digital Communicator 

 described in this manual are listed by Underwriters Laboratories Canada (ULC) for use in slave

application in conjunction with a Listed Fire Alarm Control Panel under Standard ULC-S527 (Standard for Control Units for Fire Alarm
Systems) and ULC/ORD-C693-1994 (Central Station Fire Protective Signalling Systems and Services). These Communicators should be
installed in accordance with this manual; the Canadian / Provincial / Local Electrical Code; and/or the local Authority Having Jurisdiction
(AHJ).

Industry Canada Notice:

The Industry Canada label identifies certified equipment. This certification means that the equipment meets certain telecommunications network
protective, operational and safety requirements. Industry Canada does not guarantee the equipment will operate to the user's satisfaction. Before
installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunication company.
The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above
conditions may not prevent degradations of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or
alteration made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user
to disconnect the equipment. Users should ensure for their own protection that the 

Earth Ground

 connections of the power utility, telephone

lines and internal metallic water pipe system, if present, are connected together. This is necessary both for proper operation and for protection.

CAUTION:

Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection
authority, or electrician, as appropriate.

NOTICE:

The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number
of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any
combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices
does not exceed 5.

Notice for all UDACT-9000 Sold in the U.S.A.:

Potter's 

 UDACT-9000  Digital Communicators

 described in this manual are listed by Underwriters Laboratories Inc. (ULI) for use in slave

application in conjunction with a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire Protective Signalling Systems)
and applicable section of Standard 1635 (Digital Alarm Communicator System Units). These Communicators comply with the National Fire
Protection Association (NFPA) performance requirements for DACTs and should be installed in accordance with NFPA 72 Chapter 4
(Supervising Station Fire Alarm System). These Communicators should be installed in accordance with this manual; the National Electrical
Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).

FCC Notice:

Type of Service: 

The 

Communicator

 is designed to be used on standard device telephone lines. It connects to the telephone line by means

of a standard jack called the USOC RJ-11C (or USOC FJ45S). Connection to telephone company provided coin service (central office
implemented systems) is prohibited. Connection to party lines service is subject to state tariffs.

Telephone Company Procedures: 

The goal of the telephone company is to provide you with the best service it can. In order to do this, it may

occasionally be necessary for them to make changes in their equipment, operations or procedures. If these changes might affect your service
or the operation of your equipment, the telephone company will give you notice, in writing, to allow you to make any changes necessary to
maintain uninterrupted service.

In certain circumstances, it may be necessary for the telephone company to request information from you concerning the equipment which you
have connected to your telephone line. Upon request of the telephone company, provide the FCC registration number and the ringer equivalence
number (REN); both of these items are listed on the equipment label. The sum of all of the REN’s on your telephone lines should be less than
five in order to assure proper service from the telephone company. In some cases, a sum of five may not be useable on a given line.

If Problems Arise: 

If any of your telephone equipment is not operating properly, you should immediately remove it from your telephone line,

as it may cause harm to the telephone network. If the telephone company notes a problem, they may temporarily discontinue service. When
practical, they will notify you in advance of this disconnection. If advance notice is not feasible, you will be notified as soon as possible. When
you are notified, you will be given the opportunity to correct the problem and informed of your right to file a complaint with the FCC. Contact
your telephone company if you have any questions about your phone line. In the event repairs are ever needed on the Communicator, they
should be performed by Potter Electric Signal Co. or an authorized representative of Potter Electric Signal Co.  For information contact Potter
Electric Signal Co. at the address and phone numbers shown on the first page of this document.

firealarmresources.com

Summary of Contents for UDACT-9000

Page 1: ...UDACT 9000 Digital Communicators Installation and Operation Manual 2001 by Potter Electric Signal Company September 2001 firealarmresources com...

Page 2: ...and Dimensions Page 3 Connections and Settings Page 3 Field Wiring Page 4 Power Up Procedures Page 5 System Configuration and Operation Page 8 Reporting Formats Page 10 Compatible Fire Alarm Control...

Page 3: ...arm Supervisory and Trouble information on two telephone lines when connected to a Potter Fire Alarm Control Panel FACP such as the PFC 9000 The UDACT 9000 continuously supervises the state of each of...

Page 4: ...for Fire Protective Signalling Systems and applicable section of Standard 1635 Digital Alarm Communicator System Units These Communicators comply with the National Fire Protection Association NFPA per...

Page 5: ...he Chassis Earth Ground Mounting Lug and to connect the Earth Ground Wire Lugs from the Main Chassis to the ground screw on the Backbox UDACT 9000 MAIN BOARD There are no user configurable jumpers on...

Page 6: ...the first Telephone Line via the required RJ31X Connector Line 2 Input Tip Ring To the second Telephone Line via the required RJ31X Connector Line 2 Output Tip Ring To an optional Premise Telephone o...

Page 7: ...7 Enter the passcode 2222222 for installer Enter 2 digit ITEM number to configure To scroll down list of items press or to scroll up 8 When you try to enter a 2 digit number the following screen will...

Page 8: ...Alarm Protocol by entering 54 Item number the following screen will appear 1 FA type 2 FX type UDACT type _ Press when done or to cancel Select FX by typing 2 if the Fire Alarm used is a PFC 9000 Sele...

Page 9: ...cator Reporting event Date Time The next screen is Digital Communicator Waiting for KISS Date Time If the screen stays in the Waiting for KISS mode then you should contact our Tech Support otherwise w...

Page 10: ...I II Event Logging Flush all events Terminate any in progress event reporting Remove report pending trigger i e cancel attempts to report queued events and Force event queue FIFO to empty state i e er...

Page 11: ...s Account 1 Choose which Account 1 or 2 will be the first to be attempted to be reached by the UDACT when a TROUBLE event is to be reported See ITEM 50 for a description of the UDACT report attempt op...

Page 12: ...nput circuit number For example Loop 1 address 1 will not report to the Central Station as Circuit 1 These input circuit numbers are unique and within the fire panel are automatically numbered sequent...

Page 13: ...tact Zone Fire Alarm Alarm New event 1 110 0 NNN Zone Fire Alarm restored Alarm Restore 3 110 0 NNN Zone Trouble detected Trouble New event 1 300 0 NNN Zone Trouble restored Trouble Restore 3 300 0 NN...

Page 14: ...arm New event WA NN Waterflow alarm restored Alarm Restore WH NN General Alarm Alarm New event QA NN General Alarm restored Alarm Restore QH NN Indicating Zone Trouble Trouble New event UT NN Indicati...

Page 15: ...P M Transmits user configurable Zoned Alarm Supervisory and Trouble status to a Central Monitoring Station using either Ademco Contact ID or SIA DCS Protocols M User configurable using the CFG 5000 Co...

Page 16: ...ible to repair or replace equipment which has been repaired by others abused improperly installed altered or otherwise misused or damaged in any way Unless previously contracted by Potter Potter will...

Page 17: ...TYPE EQUIVALENT CODE ALARM 1 SUPERVISORY LATCHING 2 SUPERVISORY NON LATCHING 3 WATERFLOW 4 GENERAL ALARM 5 TROUBLE 6 OUTPUT CIRCUIT TYPE SILENCEABLE SIGNAL CIRCUIT 8 NONSILENCEABLE SIGNAL CIRCUIT 9 S...

Page 18: ...____________________ Reporting Format 9 Contact ID 9 SIA ___________________________________________________________________________________________ Account 2 Identification max 6 digits _ _ _ _ _ _ A...

Reviews: