Page 1
Introduction and Features
UDACT-9000:
A single board Digital Communicator that can connect via an RS-485 Data Link on a single ribbon cable to a Potter
Fire Alarm Control Panel (FACP) such as the PFC-9000. It can transmit
Zoned
Alarm, Supervisory, and Trouble
information on two telephone lines.
T
Communicates to a FACP via
RS-485 Data Link
(UDACT-9000 with applicable Potter FACP’s).
T
User Configurable with
CFG-5000 Configuration Tool
. This includes a 4-Line LCD Display and Keypad in a rugged metal
enclosure, with a ribbon cable to connect to the Communicator.
T
Communicates to a
Central Monitoring Station
using
Ademco Contact ID
or
SIA DCS
Protocols.
T
The
UDACT-9000
can transmit
Zoned
Alarm, Supervisory, and Trouble information on two telephone lines, when connected to a
Potter Fire Alarm Control Panel (FACP) such as the PFC-9000.
The
UDACT-9000
continuously supervises the state of each of two connected Telco Lines (at approximately 1 minute intervals)
by a Line-DC level measurement. If supervision fails, a Line #1 or Line #2 Trouble event will be reported. Once a Line has been
restored, a Line Trouble Restored event will be reported. The product will
always
report events sorted in the order in which they
are received / recognized. The
UDACT-9000
is capable of reporting multiple events to a single Account number, within a single
call session. Up to 3 retries, for a single message not yet reported, will be made within a single call-attempt. A failure to
communicate to either or both Accounts will generate a corresponding event which will be queued for reporting.
firealarmresources.com