Page 3
Mechanical Installation and Dimensions
Connections and Settings
UDACT-9000 Main Board
The
UDACT-9000
board is a single PCB assembly 7-11/16” by 4-7/16”. It’s mechanical installation is determined by the Fire
Alarm Control Panel (FACP) they are being installed in, and is described in the appropriate FACP Installation Manual. Be sure
to connect a solid Earth Ground (from building system ground / to a cold water pipe) to the Chassis Earth Ground Mounting Lug,
and to connect the Earth Ground Wire Lugs from the Main Chassis to the ground screw on the Backbox.
UDACT-9000 MAIN BOARD:
There are no user configurable jumpers on these Communicators.
P1
Ribbon Cable for connecting to Potter Fire Alarm Control Panel (FACP).
P2
RS-485 Connection for future expansion.
P3
Not used.
P4
Connector for CFG-5000 Configuration Module.
I2
Status Indicator LED for Telco Line #1; Red when the line is in use, Amber when there is a line fault.
I1
Status Indicator LED for Telco Line #2; Red when the line is in use, Amber when there is a line fault.