Potter PVC 100 Installation Instructions Manual Download Page 6

PVC

 CONTROL

FIRE PHONE CONTROL

Alarm

Fault

Power

Paging Microphone

Message Display

 System Reset

Fault Silence

Paging All-Call

Lamp Test

Function

Switches & LEDs

Fire Phone

Handset

Master Panel

Controls and Displays

PAGING/ZONE CONTROL

MP 64/P panel

120 VAC

TB1

TB2

TB3

TB4

TB5

P1

P2

P3

P4

J3

1
2
3

LED3

LED2

LED1

DCC

SSC

P3

LED1

P2

P1

MFP

Master Panel Wiring

NetCom Bus

FACP
EOLR

FACP

SIGNAL CKT

FACP

I/O Control

(Supervised)

(Non-Supervised)

H

N

G

(Supervised)

24V Battery

(Supervised)

+ -

Supervised

*1

*1

All wiring with exception of
120 VAC and Battery Connection 
is Power-Limited.

Route AC power and Battery
wires to bottom-left or lower-left 
side Knock-out ..

*2

*1 All Power Limited wiring must 

maintain a min. 1/4“ separation 
from Non Power Limited wiring.

(This requirement may be waived if 
 Type FPL, FPLR or FPLP wire is used
 for Power Limited circuits)

*2 Wiring from FACP must be run

in conduit. Panels must be within
20’ and in the same room. 

*A

*A

*A - Optional wiring for 
       Style 7 supervision

ASC

TB1

P4

P3

P1

P2

P5

P5

Input

Card

PVC-II

TB1

TB2

PWR

refer to illustration

on page 9 for info

on jumper J3 placement

1

1

2

2

3

3

AC Power

Input

Transformer

to cabinet
backplate

Field wiring connections:

#6-32 wire clamp screw 14-18 AWG
#8-32 wire clamp screw 12-18 AWG

Horizontal wire entry terminal 18-26 AWG

Wire gauge determined by circuit load

Note:

 Panels may be supplied with 

transformers wired for 240 VAC for those 
regions where this is required.  Please 
refer to Ratings section for Primary 
Power differences.

Summary of Contents for PVC 100

Page 1: ...ld they occur in the system A trouble condition within the system shall cause a trouble indication to be transmitted to the FACP Distributed panels shall provide a minimum of 4 Class B Style Y speaker circuits expandable to eight total Alternately panel may be configured for 4 Class A Style Z speaker circuits Panel will provide up to 6 simultaneous audio channels up to 16 Fire Phone circuits Amplifi...

Page 2: ...resistor for supervision Attach a reference value EOLR for the speaker circuits to TB9 1 2 on MBR board This value must be placed at the end of the speaker line as well The system is shipped from the factory with 10kOhm watt EOLR 2 Connect all speaker loops UL listed devices to TB1 TB4 along the top edge of the MBR mother board in the Distributed panels Fire Phone circuit connects to TB5 TB6 on th...

Page 3: ...ystems using one amplifier per channel paging into an Evacuation Paging Zone broadcasting the Alert Signal and Message will silence the other zones also broadcasting the Alert Signal and Message if there is also a zone broadcasting the Alarm Signal and Message In other words within a single Distributed panel only two audible signals can be broadcast at one time either Alarm and Alert Signals Alarm ...

Page 4: ...ystem Reset If the fault is cleared manually the yellow led indicator can be cleared with a single click of the reset switch The All Call switch will select all available Evacuation Paging zones on the Paging Zone Control panel when clicked Individual paging zones may be deselected using the Paging Zone Control switches but a second click of the All Call switch will deselect the remainder The Syst...

Page 5: ...Voice Evacuation Speaker Circuits Fire Phone Circuit Fire Phone F I R E F I R E Head End Control PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 Master Panel Local Audio Amplifiers Voice Evacuation Speaker Circuits Fire Phone Circuit Fire Phone F I R E F I R E PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 Distributed Panel Local Audio Amplifiers Distributed ...

Page 6: ... out 2 1 All Power Limited wiring must maintain a min 1 4 separation from Non Power Limited wiring This requirement may be waived if Type FPL FPLR or FPLP wire is used for Power Limited circuits 2 Wiring from FACP must be run in conduit Panels must be within 20 and in the same room A A A Optional wiring for Style 7 supervision ASC TB1 P4 P3 P1 P2 P5 P5 Input Card PVC II TB1 TB2 PWR refer to illust...

Page 7: ...00E TB1 1 2 3 4 5 6 7 8 TB3 1 2 3 4 5 6 7 8 MESSAGE GAIN MIC GAIN FAULT NORMAL ALARM YEL GRN RED TB2 1 2 3 4 5 6 7 8 9 10 11 P2 S1 SN1 1 2 3 J2 J1 1 2 Distributed Panel Wiring PVC 25 E 50 E 100 E TROUBLE CODES When a unit goes into a Trouble Condition the Yellow LED wil remain on until the trouble is cleared The Green LED will flash a Code to indicate the type of Trouble Condition There will be a p...

Page 8: ...TB4 Not Connected TB5 Not Connected 3 TB2 PWR Factory wired 3 2 1 1 2 4 Twisted Pair Optional Style 7 Supervision Conduit Each Send Return Loop must be run in it s own conduit Style 4 Supervision J3 Removed J3 Pos 1 2 for Master Panel Pos 2 3 for Dist Panel Dist Panel DCC TB3 PVC 25E 50E 100E TB2 2 1 3 10 Factory wired J3 1 2 3 J3 1 2 3 Master Dist TB1 TB2 From Last To Next Supervised Power Limite...

Page 9: ...r Limited Non Supervised Power Limited Supervised Power Limited In normal operation FACP will supervise system by reading its EOLR Under any Fault condition in the PVC system a contact will open resulting in a Fault on the FACP bell circuit ALARM Polarity shown 1 1 2 2 3 3 jumper J1 remove before connecting batteries TB1 Ter 1 2 battery connections 1 circuit negative 2 24VDC max charging current 1...

Page 10: ... E EOL CLASS A Style Z WIRING Matching EOLR MBR TB2 TB3 TB4 TB10 J5 J6 J7 TB9 TB5 TB6 TB7 TB8 TB11 1 2 3 4 TB1 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 J8 J11 J9 J1 J2 J3 J4 LED1 P9 P10 P11 P12 P13 P14 P15 P16 P1 P2 P3 P4 P5 P6 P7 P8 3 1 1 2 3 4 50W Maximum Speaker line EOLR must be equal to Matching EOLR installed on TB9 All must be Listed EOL devices SPEAKER OUTPUT TB 1 wiring if Class A ...

Page 11: ...ximum Load Battery Charging Current 800 mA Minimum Battery Size 24V 7 AH Maximum Battery Size 24V 18 AH Battery Type 2 12V Gel Cell in Series Two 7 AH batteries is the maximum size that will fit in the Master Panel larger batteries must be housed in a separate Listed Battery enclosure For a Master Panel that is wired with a 240 VAC Transformer the following ratings apply Input Voltage 240 Vac 50 Hz...

Page 12: ...from an aux device is added into your final battery calculation Input current measurements are determined by test conditions under UL 1711 Sine represents measurements made while the unit produces a continuous non distorted sine wave of 1 KHz into the rated load of 25 50 100W at rated output voltage Alarm is the average current the unit experiences delivering an alarm signal Temporal Whoop to the r...

Reviews: