
PVC 25 / 25E
120 Vac @ 60 Hz
0.8 A @ 120 Vac
0.18 A / 1.1 A
1.1 A / 2.5 A
25 Watt
800 - 2800 Hz
25 / 70 Vrms Selectable
1.3 A Standby
2.6 A Alarm
4.2 A Sine
800mA
24V 7 AH
24V 18 AH
(2) 12V Gel Cell (in Series)
PVC 50 / 50E
120 Vac @ 60 Hz
0.5 A @ 120 Vac
0.15 A / 1.0 A
0.8 A / 1.1A
50 Watt
400 - 4000 Hz
25 / 70 Vrms Selectable
1.0 A Standby
1.3 A Alarm
5.3 A Sine
800mA
24V 7 AH
24V 18 AH
(2) 12V Gel Cell (in Series)
PVC 100 / 100E
120 Vac @ 60 Hz
1.0 A @ 120 Vac
0.16 A / 1.1 A
0.6 A / 2.0 A
100 Watt
400 - 4000 Hz
25 / 70 Vrms Selectable
1.6 A Standby
2.6 A Alarm
8.9 A Sine
800mA
24V 7 AH
24V 24 AH
(2) 12V Gel Cell (in Series)
Primary Input Voltage
Primary Input Current
*Battery Input Current Standby
Battery Input Current Alarm
Output power
Freq. Response
Output Voltage
**Optional 24 VDC input
Battery Charging Current
Minimum Battery Size
Maximum Battery Size
Battery Type
Battery Standby Operating Time: 24 - 60 Hours standby, 15 Minutes in Alarm
Output Protection: Power Limited, Open and Short Circuit protected
*Battery input current measurements are determined by test conditions. Two values are shown. First value reflects the unit with a full speaker load and no auxiliary load.
Second value reflects the unit with a full speaker load and a full auxiliary load of 0.5A in Standby and 0.75A in Alarm. Your actual load will vary depending on which and
how many auxiliary devices, ie...Zone Splitter, Remote Mic, Relays,...etc., are used. Insure that any current draw from an aux device is added into your final battery
calculation.
**Input current measurements are determined by test conditions under UL 1711. Sine represents measurements made while the unit produces a continuous non-distorted
sine wave of 1 KHz into the rated load of 25 / 50 / 100W at rated output voltage. Alarm is the average current the unit experiences delivering an alarm signal, Temporal
Whoop, to the rated load. Standby is the current draw of the unit with all normal power on and aux., terminals fully loaded. Battery Standby is current draw from the
batteries on loss of power and otherwise normal standby.
TESTING
Per NFPA 72 Chapter 7, 100% system test is required, at a minimum, annually. Additional testing may be required by the Local
Jurisdiction.
ELECTRICAL RATINGS:
PVC 25 / 50 / 100
Specifications
UL 464 520 Hz Low Frequency Signal for Sleeping Areas:
Models PVX-100 and PVX-100E are tested compliant with UL 464 520 Hz Low
Frequency Signal for Sleeping Areas with the following speakers:
Potter Signal Series:
FASPKR, SPKSTR
Gentex Series:
SSPKCLP, SSPK24WLP
System Sensor Series:
SPCW, SPCR, SPR and SPW
Models PVC-DP100, PVC-DPS100, PVC-DP100/P or PVC-DPS100/P may be used in applications requiring the 520 Hz Low frequency Signal
with the tested compliant speaker series.
For units wired with 240 VAC Transformers the following ratings apply:
Primary Input Voltage
Primary Input Current
PVC 25 / 25E
240 Vac @ 50 Hz
0.4 A @ 240 Vac
PVC 50 / 50E
240 Vac @ 50 Hz
0.27 A @ 240 Vac
PVC 100 / 100E
240 Vac @ 50 Hz
0.53 A @ 240 Vac
For technical assistance please call:
866-956-1211
5757 Phantom Dr. St. Louis, Missouri 63042
www.pottersignal.com