Potter PVC 100 Installation Instructions Manual Download Page 2

INSTALLATION

Installer must insure that all wiring and devices installed in system meet the following standards:
 

 National Electrical Code (NFPA 70)

 

 NFPA Standard 72

 

 Life Safety Code (NFPA 101)

Install equipment in a clean, dry environment, avoid installation where equipment could be subjected 
to vibration.  ** Make sure all 

Non-Power Limited

 cabling is separated from 

Power Limited 

cabling

.** 

WIRING

  

(Refer to wiring and terminal designation diagrams)

MASTER PANEL

1. Connect Netcom Bus between all panels. Maximum distance between panels is 4000’ (min 16 
AWG) or 120 Ohms max. Impedance. See page 5 for wire type.

2. Connect AC power to master panel and then connect batteries.

3.  Once power is on to the unit, connect battery wiring harness from the PWR power supply board TB-
1 Red (+) / Black (-). Observe polarity.  Minimum battery size is 7AHr. (Max 24 Ahr in a separate 
Battery cabinet) (use 2 12V batteries connected in series) *See Master panel wiring diagram on page 
6. * 

NOTE: Wiring for batteries and 120 VAC is Non Power-Limited. Care must be taken to insure that all 
Power-Limited wiring maintain a minimum spacing of  ¼" from any Non Power-Limited wiring. If 
batteries must be located in separate enclosure, provide separate conduit run for battery wiring only.

DISTRIBUTED  PANELS  
(Maximum number of Distributed Panels is 250 on a system)

1.Speaker circuits require an End of Line resistor for supervision.  Attach a “reference value” EOLR for 
the speaker circuits to TB9 - 1 & 2 on MBR board. This value must be placed at the end of the speaker 
line as well. The system is shipped from the factory with 10kOhm ½ watt EOLR.

2. Connect all speaker loops (UL listed devices) to TB1 - TB4 along the top edge of the MBR mother 
board in the Distributed panels.  Fire Phone circuit connects to TB5.-TB6 on the left side of the MBR 
Motherboard in the Distributed panels. 

3.  Connect 120 VAC, 60 Hz, power to the black and white pigtail leads from transformer primary.  
Secure ground lead to grounding stud in cabinet located on the backplate.

Note:

 Panels may be supplied with transformers wired for 240 VAC for those regions where 

this is required.  Please refer to Ratings section for Primary Power differences.

4. Once all power and circuits are connected, 

initiate a 'Global Reset' This is done by holding the "Fault 

Silence' switch in the up position while the 'System Reset' switch is clicked twice. This will rerun the  
'Power On Diagnostics' program. T

he Green LED will remain on to indicate that the PVC system  is 

fully operational and all circuits are nominal. Observe the display during the reset, it will show how 
many DP in the loop.

BATTERY MAINTENANCE

Typical battery life is approximately 3-5 years depending on usage. Always replace both
batteries with same amp hour ratings and of approximately the same age. Refer to the battery 
manufacturer's specifications for the particular battery used.  

Please read this Manual completely before installing the PVC System.

Summary of Contents for PVC 100

Page 1: ...ld they occur in the system A trouble condition within the system shall cause a trouble indication to be transmitted to the FACP Distributed panels shall provide a minimum of 4 Class B Style Y speaker circuits expandable to eight total Alternately panel may be configured for 4 Class A Style Z speaker circuits Panel will provide up to 6 simultaneous audio channels up to 16 Fire Phone circuits Amplifi...

Page 2: ...resistor for supervision Attach a reference value EOLR for the speaker circuits to TB9 1 2 on MBR board This value must be placed at the end of the speaker line as well The system is shipped from the factory with 10kOhm watt EOLR 2 Connect all speaker loops UL listed devices to TB1 TB4 along the top edge of the MBR mother board in the Distributed panels Fire Phone circuit connects to TB5 TB6 on th...

Page 3: ...ystems using one amplifier per channel paging into an Evacuation Paging Zone broadcasting the Alert Signal and Message will silence the other zones also broadcasting the Alert Signal and Message if there is also a zone broadcasting the Alarm Signal and Message In other words within a single Distributed panel only two audible signals can be broadcast at one time either Alarm and Alert Signals Alarm ...

Page 4: ...ystem Reset If the fault is cleared manually the yellow led indicator can be cleared with a single click of the reset switch The All Call switch will select all available Evacuation Paging zones on the Paging Zone Control panel when clicked Individual paging zones may be deselected using the Paging Zone Control switches but a second click of the All Call switch will deselect the remainder The Syst...

Page 5: ...Voice Evacuation Speaker Circuits Fire Phone Circuit Fire Phone F I R E F I R E Head End Control PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 Master Panel Local Audio Amplifiers Voice Evacuation Speaker Circuits Fire Phone Circuit Fire Phone F I R E F I R E PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 Distributed Panel Local Audio Amplifiers Distributed ...

Page 6: ... out 2 1 All Power Limited wiring must maintain a min 1 4 separation from Non Power Limited wiring This requirement may be waived if Type FPL FPLR or FPLP wire is used for Power Limited circuits 2 Wiring from FACP must be run in conduit Panels must be within 20 and in the same room A A A Optional wiring for Style 7 supervision ASC TB1 P4 P3 P1 P2 P5 P5 Input Card PVC II TB1 TB2 PWR refer to illust...

Page 7: ...00E TB1 1 2 3 4 5 6 7 8 TB3 1 2 3 4 5 6 7 8 MESSAGE GAIN MIC GAIN FAULT NORMAL ALARM YEL GRN RED TB2 1 2 3 4 5 6 7 8 9 10 11 P2 S1 SN1 1 2 3 J2 J1 1 2 Distributed Panel Wiring PVC 25 E 50 E 100 E TROUBLE CODES When a unit goes into a Trouble Condition the Yellow LED wil remain on until the trouble is cleared The Green LED will flash a Code to indicate the type of Trouble Condition There will be a p...

Page 8: ...TB4 Not Connected TB5 Not Connected 3 TB2 PWR Factory wired 3 2 1 1 2 4 Twisted Pair Optional Style 7 Supervision Conduit Each Send Return Loop must be run in it s own conduit Style 4 Supervision J3 Removed J3 Pos 1 2 for Master Panel Pos 2 3 for Dist Panel Dist Panel DCC TB3 PVC 25E 50E 100E TB2 2 1 3 10 Factory wired J3 1 2 3 J3 1 2 3 Master Dist TB1 TB2 From Last To Next Supervised Power Limite...

Page 9: ...r Limited Non Supervised Power Limited Supervised Power Limited In normal operation FACP will supervise system by reading its EOLR Under any Fault condition in the PVC system a contact will open resulting in a Fault on the FACP bell circuit ALARM Polarity shown 1 1 2 2 3 3 jumper J1 remove before connecting batteries TB1 Ter 1 2 battery connections 1 circuit negative 2 24VDC max charging current 1...

Page 10: ... E EOL CLASS A Style Z WIRING Matching EOLR MBR TB2 TB3 TB4 TB10 J5 J6 J7 TB9 TB5 TB6 TB7 TB8 TB11 1 2 3 4 TB1 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 J8 J11 J9 J1 J2 J3 J4 LED1 P9 P10 P11 P12 P13 P14 P15 P16 P1 P2 P3 P4 P5 P6 P7 P8 3 1 1 2 3 4 50W Maximum Speaker line EOLR must be equal to Matching EOLR installed on TB9 All must be Listed EOL devices SPEAKER OUTPUT TB 1 wiring if Class A ...

Page 11: ...ximum Load Battery Charging Current 800 mA Minimum Battery Size 24V 7 AH Maximum Battery Size 24V 18 AH Battery Type 2 12V Gel Cell in Series Two 7 AH batteries is the maximum size that will fit in the Master Panel larger batteries must be housed in a separate Listed Battery enclosure For a Master Panel that is wired with a 240 VAC Transformer the following ratings apply Input Voltage 240 Vac 50 Hz...

Page 12: ...from an aux device is added into your final battery calculation Input current measurements are determined by test conditions under UL 1711 Sine represents measurements made while the unit produces a continuous non distorted sine wave of 1 KHz into the rated load of 25 50 100W at rated output voltage Alarm is the average current the unit experiences delivering an alarm signal Temporal Whoop to the r...

Reviews: