Potter PVC 100 Installation Instructions Manual Download Page 1

Potter PVC 

Installation Instructions

OVERVIEW - Engineer’s Specification

The Potter PVC system shall include one Master Panel and one or more Distributed Panels. 
The system shall be microprocessor based, and shall be compatible for use with contact 
closures from the Fire Alarm Control Panel, (FACP). The system shall have a high-speed 
communication bus and have the capacity for 6 channels of combined audio and data on a 
single pair of wires.  The field wiring for the communication bus may be configured for either 
Style 4 or Style 7 supervision. The system shall have the capacity for Fire Fighters Phone  
communication. The system shall have a minimum capacity of 2048 monitor and control 
points. 

The Master Panel shall contain an integral microphone, dual channel digital message 
repeater, (DMR) and digital tone generator, 120 VAC power supply, and battery charger. 

Note:

 Panels may be supplied with transformers wired for 240 VAC for those regions where 

this is required.  Please refer to Ratings section for Primary Power differences.

The system shall be modular in design, and shall be expandable such that additional system 
control points may be configured. The system shall include integral self-diagnostic routines 
that shall continually monitor system status, and shall indicate the precise type of trouble 
conditions should they occur in the system.  A trouble condition within the system shall cause 
a trouble indication to be transmitted to the FACP.

Distributed panels shall provide a minimum of 4 Class "B" (Style Y) speaker circuits, 
expandable to eight  total. Alternately, panel may be configured for 4 Class "A" (Style Z) 
speaker circuits.  Panel will provide up to 6 simultaneous audio channels, up to 16 Fire 
Phone circuits.  Amplifiers will contain their own power supplies, battery chargers and provide 
auxiliary power for other components. Speaker circuits shall be supervised for short and open 
circuit conditions, and shall be able to withstand transient or continuous short-circuit 
conditions without damage to the system. 

System may be configured for General Alarm All Call operation, Alarm by Zone or 
Floor Above / Floor Below as required. Contact closures shall allow immediate broadcast of 
an alarm signal and evacuation message to the appropriate area.  Non-Alarm areas may 
receive alert tones and messages as required or activated by the FACP.

The alarm signal/evacuation message shall be broadcast until the FACP is reset, or until 
emergency personnel interrupt the broadcast with a manual page. 

To prevent unauthorized tampering, the voice evacuation system shall disable the 
microphone if the microphone is keyed continuously for 3 minutes or more.  Systems that do 
not have this feature shall not be acceptable.

P/N PV-5010  R7.16

For technical assistance please call:

866-956-1211

5757 Phantom Dr.  St. Louis, Missouri 63042

www.pottersignal.com

Summary of Contents for PVC 100

Page 1: ...ld they occur in the system A trouble condition within the system shall cause a trouble indication to be transmitted to the FACP Distributed panels shall provide a minimum of 4 Class B Style Y speaker circuits expandable to eight total Alternately panel may be configured for 4 Class A Style Z speaker circuits Panel will provide up to 6 simultaneous audio channels up to 16 Fire Phone circuits Amplifi...

Page 2: ...resistor for supervision Attach a reference value EOLR for the speaker circuits to TB9 1 2 on MBR board This value must be placed at the end of the speaker line as well The system is shipped from the factory with 10kOhm watt EOLR 2 Connect all speaker loops UL listed devices to TB1 TB4 along the top edge of the MBR mother board in the Distributed panels Fire Phone circuit connects to TB5 TB6 on th...

Page 3: ...ystems using one amplifier per channel paging into an Evacuation Paging Zone broadcasting the Alert Signal and Message will silence the other zones also broadcasting the Alert Signal and Message if there is also a zone broadcasting the Alarm Signal and Message In other words within a single Distributed panel only two audible signals can be broadcast at one time either Alarm and Alert Signals Alarm ...

Page 4: ...ystem Reset If the fault is cleared manually the yellow led indicator can be cleared with a single click of the reset switch The All Call switch will select all available Evacuation Paging zones on the Paging Zone Control panel when clicked Individual paging zones may be deselected using the Paging Zone Control switches but a second click of the All Call switch will deselect the remainder The Syst...

Page 5: ...Voice Evacuation Speaker Circuits Fire Phone Circuit Fire Phone F I R E F I R E Head End Control PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 Master Panel Local Audio Amplifiers Voice Evacuation Speaker Circuits Fire Phone Circuit Fire Phone F I R E F I R E PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 PVC 25 PVC 50 PVC 100 TB1 TB3 TB2 Distributed Panel Local Audio Amplifiers Distributed ...

Page 6: ... out 2 1 All Power Limited wiring must maintain a min 1 4 separation from Non Power Limited wiring This requirement may be waived if Type FPL FPLR or FPLP wire is used for Power Limited circuits 2 Wiring from FACP must be run in conduit Panels must be within 20 and in the same room A A A Optional wiring for Style 7 supervision ASC TB1 P4 P3 P1 P2 P5 P5 Input Card PVC II TB1 TB2 PWR refer to illust...

Page 7: ...00E TB1 1 2 3 4 5 6 7 8 TB3 1 2 3 4 5 6 7 8 MESSAGE GAIN MIC GAIN FAULT NORMAL ALARM YEL GRN RED TB2 1 2 3 4 5 6 7 8 9 10 11 P2 S1 SN1 1 2 3 J2 J1 1 2 Distributed Panel Wiring PVC 25 E 50 E 100 E TROUBLE CODES When a unit goes into a Trouble Condition the Yellow LED wil remain on until the trouble is cleared The Green LED will flash a Code to indicate the type of Trouble Condition There will be a p...

Page 8: ...TB4 Not Connected TB5 Not Connected 3 TB2 PWR Factory wired 3 2 1 1 2 4 Twisted Pair Optional Style 7 Supervision Conduit Each Send Return Loop must be run in it s own conduit Style 4 Supervision J3 Removed J3 Pos 1 2 for Master Panel Pos 2 3 for Dist Panel Dist Panel DCC TB3 PVC 25E 50E 100E TB2 2 1 3 10 Factory wired J3 1 2 3 J3 1 2 3 Master Dist TB1 TB2 From Last To Next Supervised Power Limite...

Page 9: ...r Limited Non Supervised Power Limited Supervised Power Limited In normal operation FACP will supervise system by reading its EOLR Under any Fault condition in the PVC system a contact will open resulting in a Fault on the FACP bell circuit ALARM Polarity shown 1 1 2 2 3 3 jumper J1 remove before connecting batteries TB1 Ter 1 2 battery connections 1 circuit negative 2 24VDC max charging current 1...

Page 10: ... E EOL CLASS A Style Z WIRING Matching EOLR MBR TB2 TB3 TB4 TB10 J5 J6 J7 TB9 TB5 TB6 TB7 TB8 TB11 1 2 3 4 TB1 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 J8 J11 J9 J1 J2 J3 J4 LED1 P9 P10 P11 P12 P13 P14 P15 P16 P1 P2 P3 P4 P5 P6 P7 P8 3 1 1 2 3 4 50W Maximum Speaker line EOLR must be equal to Matching EOLR installed on TB9 All must be Listed EOL devices SPEAKER OUTPUT TB 1 wiring if Class A ...

Page 11: ...ximum Load Battery Charging Current 800 mA Minimum Battery Size 24V 7 AH Maximum Battery Size 24V 18 AH Battery Type 2 12V Gel Cell in Series Two 7 AH batteries is the maximum size that will fit in the Master Panel larger batteries must be housed in a separate Listed Battery enclosure For a Master Panel that is wired with a 240 VAC Transformer the following ratings apply Input Voltage 240 Vac 50 Hz...

Page 12: ...from an aux device is added into your final battery calculation Input current measurements are determined by test conditions under UL 1711 Sine represents measurements made while the unit produces a continuous non distorted sine wave of 1 KHz into the rated load of 25 50 100W at rated output voltage Alarm is the average current the unit experiences delivering an alarm signal Temporal Whoop to the r...

Reviews: