PSN-106:15
PSN-106, PSN-64, PSB-10 • 5403590 • REV A • 12/09
Secondary Power Supply Requirements Table
Service
Use
Standby
Time
Alarm
Time
NFPA
72
• Central Station (PPU)
24 hours
5 minutes
• Local
24 hours
5 minutes
Calculation Table
1 2
3
4
5
6
Module/Device
Quantity
Standby mA Per Unit
Total Standby Current
Alarm mA Per Unit
Total Alarm Current
x 0.001
x 0.001
Total mA
Convert to A
Total A
5 min/12 or 10 min/6
Total Alarm AH
+ Total Standby AH
Total AH
Effi ciency Factor
Required AH
Total mA
Convert to A
(* Refer to Maximum allowable standby current)Total A
Multiply by hours
Total Standby AH
÷ ___
Use a battery with a higher AH rating than Required AH
÷ 0.85
x ___
Battery Calculation Worksheet
Standby current for the PSN-106 is 75 milli-amps.
PSN-106 1
75
75
75
75
Battery Size
UL 24-hour
ULC 24-hour
7 AH
.213 Amps
.213 Amps
18 AH
.603 Amps
.603 Amps
33 AH
1.134 Amps
.603 Amps
55 AH
1.913 Amps
.603 Amps
* Maximum Allowable Standby Current (24-hour standby time)