![Potter PSB-10 Installation, Operation And Instruction Manual Download Page 14](http://html.mh-extra.com/html/potter/psb-10/psb-10_installation-operation-and-instruction-manual_1582934014.webp)
PSN-106:10
PSN-106, PSN-64, PSB-10 • 5403590 • REV A • 12/09
Wire Routing
A minimum of ¼ inch separation must be maintained between Power Limited, Non-Power Limited, and High Voltage wiring. See
illustration for suggested wire routing
Reference EOL
The PSN-106 uses a standard 5.1k EOL resistor (Potter part number 3005013).
In retrofi t applications where a value other than 5.1k is already in use, a reference EOL input is provided. Simply connect a
matching EOL resistor to the reference EOL input. All NAC wiring will then be supervised based on this value. Any EOL value
from 2.0k to 27k can be used.
If no reference EOL is connected, 5.1k is assumed.
Summary of Contents for PSB-10
Page 2: ...2 PSN 106 PSN 64 PSB 10 5403590 REV A 12 09 ...
Page 20: ...PSN 106 16 PSN 106 PSN 64 PSB 10 5403590 REV A 12 09 This page intentionally left blank ...
Page 36: ...PSN 64 16 PSN 106 PSN 64 PSB 10 5403590 REV A 12 09 This page intentionally left blank ...
Page 46: ...This page intentionally left blank ...
Page 47: ......
Page 48: ......