Caution: 

Please be aware of the temperature surge risk when setting a 

large temperature gap between TL--TS /TS--TH. Recommend to set 

the gap smaller than 10 degrees. The tighter gap the more stable real 

temperature. 

Note: 

Please check and test your setting every time before leaving 

controller to a long-term running.   

 

6.2

 

Temperature Alarm Setting (AL, AH) 

 

When measured temperature ≤ AL, low 

temperature alarm will be 

triggered, buzzer will alarm until temperature

AL or any key is 

pressed. 

When measured temperature ≥ AH, high temperature alarm will be 

triggered, buzzer will alarm until temperature

AH or any key is 

pressed. 

Note:

 

If you set the AL ≥ TL, then the real low temperature alarm 

point is TL-

0.5℃

If you set the AH ≤ TH, the real high alarm point is 

TH+0.5℃

 

6.3 Compressor Protection Time (PT) 

Under cooling mode, compressor protection will keep the refrigeration 

off between cycles to protect your compressor. That means 

compressor won't start refrigeration immediately, but waiting for a 

delay time if it falls into the PT time frame. Delay time will be 

Summary of Contents for TC-15A

Page 1: ...User Manual Model No TC 15A Thank you for purchasing the Temperature Controller by Poniie Please read this manual carefully before using this product ...

Page 2: ... the metal NTC probe will be slowly damaged by salt water or acid alkali water 1 6 NOTE If the relays are used over capability contact fusing or burning may occur Please use the relays within their rated load 2 Overview What is TC 15A TC 15A is an easy to use safe and reliable dual relay output temperature controller It can be connected to both heating and cooling loads at the same time to control...

Page 3: ...delay protection High and low temperature alarm Faulty sensor alarm 3 Specification Temperature Control Range 40 0 99 9 Temperature Resolution 0 1 Temperature Accuracy 1 0 20 0 70 0 Input Power 100 125V 50 60Hz Maximum Output Load 15A 100 125V 1650W 110V Buzzer Alarm Low and High Temperature Alarm Sensor Type NTC sensor Control Panel Cable Length 1 5m 4 9ft Input Power Cable Length 1 7m 5 6ft Sens...

Page 4: ...for both heating and cooling It can be taken as the central temperature point in setting mode displays setting value of menu codes When controller working normally press key the setting Low Temperature TL point is displayed press key the setting High Temperature TH point is displayed The screen will auto return to normal display after 2 seconds 4 2 How to set parameters Basic Setting Mode Press SE...

Page 5: ...conds to enter the advanced setting mode You are able to set AL Low Alarm Temperature point AH High Alarm Temperature point PT Compressor Protection Time CF Display setting and CA Calibration function parameters After settings press hold down SET key 3 seconds or leave it with no operation 15 seconds to save parameter changes and return to working mode User Tips 1 Under setting mode press SET key ...

Page 6: ... Flow Chart Basic Setting Mode Advanced Setting Mode Short press SET Press hold SET for 3s SET 3S SET 3S TL SET 23 0 SET AL 20 0 SET AH 90 0 SET PT 2min CF CA 0 TS 25 0 TH 27 0 SET SET Working Normally SET SET ...

Page 7: ...0 0 6 5 6 1 Temperature Control Range Setting TL TS TH This controller has a heating and cooling control outlets However you can only use the heating or cooling side for your project When measured temperature TL system enter heating state the heating outlet relay starts to work when it heats up to shutdown point TS the heating relay stops When measured temperature TH system enter cooling state the...

Page 8: ...uzzer will alarm until temperature AL or any key is pressed When measured temperature AH high temperature alarm will be triggered buzzer will alarm until temperature AH or any key is pressed Note If you set the AL TL then the real low temperature alarm point is TL 0 5 If you set the AH TH the real high alarm point is TH 0 5 6 3 Compressor Protection Time PT Under cooling mode compressor protection...

Page 9: ...ration function to align the measured temperature and actual temperature The corrected temperature equals to temperature before calibration plus corrected value corrected value can be positive 0 or negative value 7 Error Description 1 If LED displays flashing code AL or AH please kindly check your AL or AH setting in advanced setting mode Buzzer will alarm until temperature fall into setting range...