LAB964R, Issue 4, May 2014
Page 2
Warnings & Safety Information
IMPORTANT!
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE COMMENCING INSTALLATION
1. Do not install this appliance in areas where the following may be present or occur:
•
Excessive oil or a grease laden atmosphere
•
Corrosive or flammable gases, liquids or vapours
•
Be subject to direct water spray
•
Ambient temperatures higher than 50ºC and lower than -25ºC
•
Possible obstructions that may hinder access or removal of the unit
2. This appliance is not intended for use by young children or infirm persons without adequate supervision.
3. All wiring must be in accordance with prevailing national regulations, for example the current IEE Wiring Regulations
BS7671. The electrical installation should be inspected and tested by a suitably qualified person after completion.
4. The appliance should be provided with a local double pole fused spur fitted with a 3 Amp fuse and a minimum contact
separation of at least 3mm.
5. Ensure that the mains supply (Voltage and Frequency) complies with the rating label.
6. This appliance must be earthed.
7. When installing the appliance, care should be taken not to damage any hidden utilities.
8. The installer is responsible for the installation and electrical connection of the
CMX
system on site. It is the responsibility
of the installer to ensure that the equipment is safely and securely installed and left only when electrically and mechanically
safe.
9. All regulations and requirements must be strictly followed to prevent hazards to life and property, both during and after
installation and any subsequent servicing or maintenance.
10. In dwellings where it is intended to install open-flue appliances and extract ventilation, the combustion appliance should
be able to operate safely, whether or not the fans are running. A way of showing compliance with The Building Regulations
in these circumstances would be to follow the installation guidance shown below, and to show by tests that combustion
appliances operate safely, whether or not the fans are running.
A. For gas appliances: where a room contains an open-flue appliance, the extract rate should not exceed
20l/s (72m³/h).
B. For oil appliances: where a room contains an open-flue appliance, the extract rate should be limited to
40l/s (144m³/h) for an appliance with a pressure jet burner and 20l/s (72m³/h) for an appliance with a
vaporising burner.
C. For solid fuel appliances: avoid installing extract ventilation in the same room.
Further reference should be made to Approved Document J of The Building Regulations.
11. This appliance should not be directly connected to a tumble dryer or cooker hood.
12. A supply of fresh replacement air must be drawn from the exterior of the property. Further reference should be made to
Approved Document F of The Building Regulations.
13. The extracted air must be expelled to the exterior of the property.
14. Extract ceiling valves should be positioned at least 300mm from internal walls to allow airflow measuring equipment to
fit correctly over the valves.
15. Ducting should be insulated where it passes through unheated spaces and voids (e.g. loft spaces) to reduce the
possibility of condensation forming.