Electrical

 

 

5.1 

WARNING: This appliance must be earthed.  

 
5.2 

Important: All wiring must be carried out by a qualified electrician and conform to the prevailing 
national regulations, for example the latest edition of BS7671: IEE Wiring Regulations. 

 

5.3 

This appliance is suitable for 230V 50Hz single phase supply only, fused at 3 Amps. 

 

5.4 

A double-pole switch having a minimum contact separation of 3mm must be used to provide isolation 
for the appliance. 

 
5.5 

Sensor diagrams are shown on page 9. 

 
5.6 

External wiring (1.5mm² max.) and isolators to be supplied by others. 

 
 

Wiring 

 
6.1 

Remove the cover of the wiring centre by removing the six retaining screws while taking care not to 
dislodge any of the pre-wired cables. 

 
6.2 

Make the wiring connections – see diagram below. 

 
6.3 

Refit the wiring centre cover. 

 
 
 
 
 

Summary of Contents for Silavent CMX

Page 1: ...ructions must be given to the householder DO NOT SWITCH OFF THE UNIT it is designed to run continuously If the unit is switched off indoor pollutants and moisture levels may increase which could endan...

Page 2: ...tly followed to prevent hazards to life and property both during and after installation and any subsequent servicing or maintenance 10 In dwellings where it is intended to install open flue appliances...

Page 3: ...4 2 Physical specification Page 5 3 Installation Page 5 4 Ducting guidelines Page 6 5 Electrical Page 7 6 Wiring Page 7 7 Remote switch wiring diagrams Page 8 8 External sensor wiring diagrams Page 9...

Page 4: ...t manual OCCUPIED UNOCCUPIED LOW BOOST switch code ANC849A Manual BOOST and UNOCCUPIED selection switches OCCUPIED LOW speed is engaged upon connection of mains supply UNOCCUPIED speed is intended to...

Page 5: ...fixing the CMX appliance in position 3 2 When accepting delivery of the CMX appliance inspect for transit damage If in doubt call our Customer Service team on 08443 715523 3 3 The CMX appliance can be...

Page 6: ...with Approved Document F of The Building Regulations 4 5 When passing through a fire stopping wall or fire compartment wall Domus FireBrake intumescent duct connectors should be used in order to comp...

Page 7: ...0V 50Hz single phase supply only fused at 3 Amps 5 4 A double pole switch having a minimum contact separation of 3mm must be used to provide isolation for the appliance 5 5 Sensor diagrams are shown o...

Page 8: ...4 May 2014 Page 8 7 Remote switch wiring diagrams ANC848A ANC849A ANC850A ANC848A Low Boost functions ANC850A Low Boost Purge functions ANC849A Occupied Unoccupied Low Boost functions BOOST PURGE BOO...

Page 9: ...IMPORTANT CONNECTIONS TO THESE TERMINALS MUST HAVE CLEARLY LABELLED ISOLATORS SITUATED ADJACENT TO THE WIRING CENTRE ANC108A OVERRUN TIMER ELE150R SWITCHED LIVE EXTENSION BOARD ANC802A HUMIDISTAT WITH...

Page 10: ...airflow rate will need to be recorded on the Inspection Checklist and Airflow Measurement Test Sheet A completed copy must accompany these instructions and be handed over to the dwelling s owner upon...

Page 11: ...iated parts and components including any ducting using reasonable skill and care and in accordance with the instructions provided with it unless the original installation maintenance or repair which g...

Page 12: ...Email Polypipe Ventilation Sandall Stones Road Kirk Sandall Industrial Estate Kirk Sandall Doncaster DN3 1QR UK Tel 08443 715523 Fax 08443 715524 International Tel 44 0 1302 348878 International Fax...

Reviews: