12
11. Installer Menus
There are 2 Installer Menus which can be accessed by pressing
and holding the either :
Programme key
(
•
)
Programmes 1 to 12
or the escape key
( )
programmes 21 to 33
Installer Programmes 1 to 12
N°
Default value & other possibilities
01
Deg: Type of degrees displayed
°C Celsius
°F Fahrenheit
02
__:__ Selection of the clock
24H (24:00)
12H (12:00 AM /PM)
03
DST Automatic Daylight Summetime
YES or NO
04
AirS: Instantaneous value of ambient sensor
05
Airc:
Calibration of the internal probe
The calibration can done after 1 working
day with the same setting temperature in
accordance with the following description:
Put a thermometer in the room at 1.5M
distance from the floor (like the thermostat) and
check the real temperature in the room after 1
hour.
When you enter on the calibration parameter
“
no
” is displayed on the right to indicate no
calibration has made.
To enter the value read on the thermometer,
use the
(-)
or
(+)
keys to enter the real value.
Once, press
(OK)
to confirm.
The message “
Yes
” should be displayed, the
value will be stored in the internal memory.
If you need to erase a calibration press on the
escape key
( )
.
The old value will be erased and the message
“
no
” will be displayed.
Note
: Only the heating element managed
by the thermostat must be run during the
complete step of the calibration.
06
EXTS – Instananeous value of floor sensor
08
HG – Frost protection temperature 10deg C
09
ITCS:
The
Intelligent Temperature Control System
or Optimun start programme will activate
your system in advance to assure the desired
temperature at the hour programmed
08
Clr ALL:
Factory setting
All parameters (Time, program...) will be
reloaded with default setting values.
Note
Ensure you that you have all necessary
elements to re-start before use this function.
09
Hyst:
Hysteresis value
0.5°C or 1°C
10
Software version
Vers __._
11
End:
Exit the Installers menu
Press
(OK)
key to exit installater menu and
return to normal operation.
N°
Default value & other possibilities
21
out NC/ NO - Type of actuator used ,set as
normally closed (NC)
22
PUMP – YES/NO Pump exercise programme
every 12 hrs
23-
Settings for External sensor as previously
25
described
26
Type HYS/ rEG – Type of regulation , hysteresis /
proportional band
27
HYSt0.05/1.1 Hysteresis band gap
28
tON 02 = relay ON anti short cycle in minutes
29
tOFF 02= relay OFF anti short cycle in minutes
31
CP0.00 = advanced parameter if internal
sensor id heated by a heating element ,
compensation value in deg c at100% power
32
Clr EEP +hold
OK
= will reset non volatile
memory programs to factory
33
End +
OK
to exit the Installer Menu
Installer menus 21 to 33