2)
For zone touchpads, pressing button after
the setting of all three parameters will return to the
normal operation mode.
3)
For the master touch
pad, pressing button
will return to the normal operation mode.
2. Initialisation of Touchpad Address
Each touchpad (zone) must have a unique address
from 1 to 16 to be identified by the main controller.
The touchpad has a factory default of ‘No addr’ that
cannot be identified by the main controller.
The touchpad needs to be initiated by allocating
a unique address. The allocation can be carried
out by pressing or button, and then
pushing (zone touchpad) or
(master touchpad) button.
Please note that each touchpad (zone) must have
a unique address. The same address for any of two
touchpads will cause communications problem
between the main controller and touchpads, and
the touchpad LCD shows ‘Check Address’
3. Room Temperature Sensor
Each touchpad has an onboard sensor to measure the temperature of
the room for temperature control. The sensor can be calibrated to provide
more accurate temperature control.
1)
Usin
g an accurate probe to measure the
temperature of the area user wants to calibrate
and record the value.
Page 9