Page 8
2)
Take off the small cover on the top of the
damper controller and set a special address
for the bypass damper controller.
3)
Use a pre-tested control cable to
connect the bypass damper
controller to the ‘point’ socket on the
main controller board. Make sure
the red light on the damper controller
is on. Otherwise, check the cable and
the connection.
COMMISSIONING
The Zonemaster VAV system has several parameters that must be set in
the commissioning stage.
Zone touchpad (3 button) can only set three zone parameters:
1)
Touchpad Address
2)
Temperature Sensor
3)
Minimum Ventilation
Master touchpad (6 button) can set the above parameters and three
system parameters listed below:
1)
Supply Air Safety High & Low Limits
2)
Spill Bypass/Air Setpoint
3)
Naming Zones
1. Initiating and Exit Setting Process
1)
Hold down both and buttons for about
5 seconds until the LCD displays ‘Setting’ on the
top line of the LCD screen.