7) Troubleshooting Guide

PROBLEM

SUGGESTED ACTION

Dampers have no  

response when turned on 

or off

•  Check if the ‘Safety is Activated’ error is displayed. High limit (Heating)  

  or Low limit (Cooling) may have reached. Check the air-conditioner to 

  see if it is operating normally. ZoneTouch V2 system will resume to  

  operational after the supply air temperature is within safety range.
•   *Check if Supply air sensor is plugged in the mainboard and High Limit  

  & Low Limit is enabled. If the sensor is not plugged in, plug the  

  sensor and the system will be operational after a minute. If the sensor  

  is not required, disable High limit and Low limit from touchpad and  

  system will return to operational in a minute.
•   *Check if LEDs on the main module light up for relevant zones when  

  the zone dampers are being turned On/Off. If Green/Red LEDs are not  

  activated for the respective zone, the main module may be faulty, replace it.
•  *Check if the cable from touchpad to the main control module is faulty.  

  If it is a faulty cable, then the cable might have to be replaced.

Some zones cannot  

be turned off

•  Check if ‘Spill is activated’ is displayed on the LCD screen. 
•  Check if ‘Spill’ status is displayed for the Group status in the home  

  screen. Opening other zones will rectify the error 
•  *If all zones are turned on but the total opening percentage doesn’t  

  meet the required spill percentage, then the SPILL warning message  

  will be displayed. Increasing the opening percentage of a few zones  

  will resolve the issue.
•  *Check spill set-point.

No display on the LCD

•   *Check if the cable is plugged in properly. Unplug the cable and  

  reconnect it.
•   *Check if there is power to the unit.

LCD Display  

Corrupted

•  Reset LCD by holding RESET button at the bottom of the Touchpad for  

  2s.
•  *If error is still not resolved, reset touchpad by unplugging the cable  

  from behind and then reconnect it after a couple minutes. If the  

  corrupted display remains, power off/on the mainboard. Otherwise,  

  replace the touchpad.

Some zones are  

not operational

•   *Check Grouping and find out if the right zones have been assigned to  

  the right groups and have been turned ON/OFF in Zoning section.
•   *Check if the total group number and zone number are correct.
•   *Check if the LEDs on the main module light up for the relevant zones  

  when the zone dampers are turned On/Off. If there is no response,  

  there might be a faulty cable and the cable would have to be replaced.  

  If the zone is still non-functional then there might be a faulty damper  

  motor.

*:

 

These checks in the guide should be carried out by qualified personnel.  

 

If you have any doubt regarding the above please contact your installer.

Summary of Contents for ZoneMaser ZoneTouch V2

Page 1: ...ZoneTouch V2 Zone Control System User Manual www polyaire com au 2014 Polyaire Pty Ltd...

Page 2: ...ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM User Manual II...

Page 3: ...p 7 5 User Settings 8 5 1 Time Date setup 8 5 2 Owner s Name 9 5 3 Turbo Group 9 5 4 Temperature Display 10 5 5 Touch Tone 10 6 Information Sheets 11 7 Troubleshooting Guide 14 8 Specifications 15 TAB...

Page 4: ...nes automatically resume their original on off state once power is restored after power outage 1 A zone is the area where air supply is controlled by one motorized damper 2 A group is a few zones grou...

Page 5: ...ouch tone status and ZoneTouch logo as shown in Figure 1 NOTE The touch screen will go to the sleep mode after 90 seconds of inactivity In sleep mode the screen is blank Touching any area of the scree...

Page 6: ...p will open or close accordingly b The group status can be set to TURBO active when the group is specified as a turbo group refer to 5 3 and the grey turbo indicator will turn blue to indicate the TUR...

Page 7: ...nt event time slots NOTE A group can have up to a maximum of 4 zones Your installer would have already set up your zones and groups 3 2 Adjusting airflow for a group The damper opening percentage for...

Page 8: ...he home screen to enter Programming screen Figure 4 Figure 4 Figure 6 b Touch a day option radio button to select Monday Friday Saturday or Sunday program to modify Touch the time switch radio button...

Page 9: ...uch the program field of a group to show all program options Figure 8 Touching a program option will assign the program to the group Figure 9 Each group can be assigned with one program from program1...

Page 10: ...e Touching button will go back to the home screen from User setting pages Figure 11 Figure 12 5 User Settings Figure 13 Figure 14 5 1 Time Date setup a Touch on the User Settings screen Figure 12 to e...

Page 11: ...l other groups dampers opening positions are reduced by 50 of their open percentage value This will bring a large volume of extra air into the designated area and cool or heat the area quicker Typical...

Page 12: ...screen Below images show the enabled status Figure 17 and disabled status Figure 18 of temperature display 5 5 Touch Tone The touch tone feature allows to either enable or disable the tone when the s...

Page 13: ...ormation Sheets These should be filled out by the installer Total Groups Bypass Damper Installed Supply Air Sensor Installed Yes No Yes No Group Group Name Zones Included Turbo Function 1 2 3 4 5 6 7...

Page 14: ...ROL SYSTEM User Manual 12 Installer Contact Number Date Zone Balance Percentage Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone A Zone B Zone C Zone D Zone E Zone F Zone G Table 4...

Page 15: ...Off time 2 Monday Friday Saturday Sunday Groups PROGRAM 2 On time 1 Off time 1 On time 2 Off time 2 Monday Friday Saturday Sunday Groups PROGRAM 3 On time 1 Off time 1 On time 2 Off time 2 Monday Fri...

Page 16: ...the Group status in the home screen Opening other zones will rectify the error If all zones are turned on but the total opening percentage doesn t meet the required spill percentage then the SPILL war...

Page 17: ...Altitude 0 to 2000 meters Operating relative humidity 10 to 80 Avoid static electricity hazards Avoid electromagnetic radiation sources Avoid dust contamination Avoid highly corrosive environments Zo...

Page 18: ...ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM User Manual 16...

Page 19: ...ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM User Manual 17...

Page 20: ...ZMZT2_USER_V1 0 POLYAIRE PTY LTD 11 13 WHITE ROAD GEPPS CROSS SOUTH AUSTRALIA 5094 TEL 08 8349 8466 FAX 08 8349 8446 www polyaire com au...

Reviews: