7) Troubleshooting Guide
PROBLEM
SUGGESTED ACTION
Dampers have no
response when turned on
or off
• Check if the ‘Safety is Activated’ error is displayed. High limit (Heating)
or Low limit (Cooling) may have reached. Check the air-conditioner to
see if it is operating normally. ZoneTouch V2 system will resume to
operational after the supply air temperature is within safety range.
• *Check if Supply air sensor is plugged in the mainboard and High Limit
& Low Limit is enabled. If the sensor is not plugged in, plug the
sensor and the system will be operational after a minute. If the sensor
is not required, disable High limit and Low limit from touchpad and
system will return to operational in a minute.
• *Check if LEDs on the main module light up for relevant zones when
the zone dampers are being turned On/Off. If Green/Red LEDs are not
activated for the respective zone, the main module may be faulty, replace it.
• *Check if the cable from touchpad to the main control module is faulty.
If it is a faulty cable, then the cable might have to be replaced.
Some zones cannot
be turned off
• Check if ‘Spill is activated’ is displayed on the LCD screen.
• Check if ‘Spill’ status is displayed for the Group status in the home
screen. Opening other zones will rectify the error
• *If all zones are turned on but the total opening percentage doesn’t
meet the required spill percentage, then the SPILL warning message
will be displayed. Increasing the opening percentage of a few zones
will resolve the issue.
• *Check spill set-point.
No display on the LCD
• *Check if the cable is plugged in properly. Unplug the cable and
reconnect it.
• *Check if there is power to the unit.
LCD Display
Corrupted
• Reset LCD by holding RESET button at the bottom of the Touchpad for
2s.
• *If error is still not resolved, reset touchpad by unplugging the cable
from behind and then reconnect it after a couple minutes. If the
corrupted display remains, power off/on the mainboard. Otherwise,
replace the touchpad.
Some zones are
not operational
• *Check Grouping and find out if the right zones have been assigned to
the right groups and have been turned ON/OFF in Zoning section.
• *Check if the total group number and zone number are correct.
• *Check if the LEDs on the main module light up for the relevant zones
when the zone dampers are turned On/Off. If there is no response,
there might be a faulty cable and the cable would have to be replaced.
If the zone is still non-functional then there might be a faulty damper
motor.
*:
These checks in the guide should be carried out by qualified personnel.
If you have any doubt regarding the above please contact your installer.
Summary of Contents for ZoneMaser ZoneTouch V2
Page 1: ...ZoneTouch V2 Zone Control System User Manual www polyaire com au 2014 Polyaire Pty Ltd...
Page 2: ...ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM User Manual II...
Page 18: ...ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM User Manual 16...
Page 19: ...ZONEMASTER ZONETOUCH V2 ZONE CONTROL SYSTEM User Manual 17...