background image

 

IK

E301

001GB

 

3

 

1

 

PURPOSE

 

The

 

DOT

4046

 

multi

sensor

 

addressable

 

smoke

 

and

 

heat

 

detector

 

is

 

designed

 

for

 

detection

 

of

 

a

 

fire

 

initial

 

phase

 

when

 

a

 

smoke

 

occurs

 

and/or

 

temperature

 

rise

 

may

 

be

 

observed.

 

The

 

detector

 

is

 

characterised

 

by

 

a

 

high

 

resistance

 

level

 

against

 

wind

 

movement

 

and

 

pressure

 

change.

  

The

 

DOT

4046

 

multi

sensor

 

addressable

 

detectors

 

are

 

intended

 

to

 

operate

 

in

 

the

 

POLON

 

4000

 

fire

 

detecting

 

and

 

alarm

 

system

 

control

 

panel

 

addressable

 

lines.

  

They

 

are

 

equipped

 

with

 

internal

 

short

 

circuit

 

isolators.

 

 

2

 

TECHNICAL

 

SPECIFICATIONS

 

Operating

 

voltage

 

16.5

 

V

 

÷

 

24.6

 

V

 

Maximum

 

current

 

draw

 

≤ 

150

 

µA

 

Maximum

 

installation

 

height

 

*)

 

7.5

 

m

  

Maximum

 

supervised

 

area

 

*)

 

40

 

m

2

  

Operating

 

temperature:

 

 

for

 

‘1’

 

and

 

‘2’

 

modes

  

 

 

 

  

from

 ‐

25

 

°C

 

to

 

+50

 

°C

 

 

for

 

‘3’

 

and

 

‘4’

 

modes

  

 

 

 

  

from

 ‐

25

 

°C

 

to

 

+65

 

°C

 

Allowable

 

relative

 

humidity

 

up

 

to

 

95

 

%

 

at

 

40

 

°C

 

Dimensions

 

(without

 

base)

 

Ø

 

115

 

mm

 

x

 

43

 

mm

 

Number

 

of

 

basic

 

operation

 

modes

 

4

 

Mass

 

(without

 

base)

 

0.2

 

kg

 

Standard

 

colour

 

white

 

Address

 

coding

 

method

 

programmable

 

at

 

the

 

control

 

panel

 

Test

 

fire

 

detection

 

suitability

 

TF1,

 

TF2,

 

TF3,

 

TF4,

 

TF5,

 

TF6,

 

TF8.

 

*)

 

see

 

design

 

guidelines

 

3

 

SAFETY

 

CONDITIONS

  

3.1

 

Repairs

 

and

 

maintenance

  

Any

 

maintenance

 

works

 

or

 

periodic

 

inspections

 

shall

 

be

 

executed

 

by

 

skilled

 

personnel

 

employed

 

by

 

companies

 

authorised

 

and

 

trained

 

by

 

POLON

ALFA.

  

Any

 

repairs

 

must

 

be

 

carried

 

out

 

by

 

the

 

manufacturer.

 

POLON

ALFA

 

bears

 

no

 

responsibility

 

for

 

the

 

operation

 

of

 

any

 

apparatus

 

being

 

repaired

 

by

 

unauthorised

 

personnel.

 

 

3.2

 

Works

 

at

 

height

  

Any

 

detector

 

installation

 

works

 

carried

 

out

 

at

 

height

 

must

 

be

 

executed

 

with

 

particular

 

care

 

utilising

 

tools

 

and

 

machinery

 

in

 

good

 

working

 

condition.

  

Special

 

attention

 

shall

 

be

 

given

 

to

 

stability

 

of

 

ladders,

 

elevators,

 

lifts,

 

etc.

 

Summary of Contents for DOT?4046

Page 1: ...POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM DOT 4046 MULTI SENSOR SMOKE AND HEAT DETECTOR Installation and Maintenance Manual IK E301 001GB IIIB Edition ...

Page 2: ...fa pl web site 1438 Polon Alfa Spółka z ograniczoną odpowiedzialnością Sp k 155 Glinki Street PL 85 861 Bydgoszcz POLAND 05 1438 CPD 0015 EN 54 7 DOT 4046 Multi sensor Smoke and Heat Detector utilising scattered light effect and heat sensor addressable detachable Application fire safety Technical data IK E301 001GB manual Read the manual carefully before the detector assembling and commissioning A...

Page 3: ... modes from 25 C to 65 C Allowable relative humidity up to 95 at 40 C Dimensions without base Ø 115 mm x 43 mm Number of basic operation modes 4 Mass without base 0 2 kg Standard colour white Address coding method programmable at the control panel Test fire detection suitability TF1 TF2 TF3 TF4 TF5 TF6 TF8 see design guidelines 3 SAFETY CONDITIONS 3 1 Repairs and maintenance Any maintenance works ...

Page 4: ...ire alarm control panel and the DOT 4046 detectors is provided through a two wire addressable detection line A unique fully digital communications protocol enables passing any information from the control panel to the detector and inversely e g evaluation of surrounding conditions smokiness temperature tendency of its change as well as current temperature analogue value and smokiness density The d...

Page 5: ... only a smoke detector DOR operates 6 mode in which only a heat detector TUP in class A1R operates 7 mode in which only a heat detector TUP in class BR operates 7 OPERATION AND SERVICING CONDITIONS During the detectors operation it is obligatory to avoid creation of dew or rime on the detector surface as well as to protect against excessive contamination with dust For the period of repair works th...

Page 6: ...smantling is shown on Fig 1 In order to dismantle the detector it is necessary to a pressing the net long tongue turn the cover right in the basket until it is taken out b remove and bend aside the thermistor basis from the labyrinth c unfasten two screws that fix the labyrinth and take the labyrinth out d perform the necessary cleaning A delicate brush as well as vacuum cleaner are recommended fo...

Page 7: ... see the POLON 4000 system control panels Installation and Maintenance Manuals The detectors are installed in the 40 model range bases The detection line connection is presented in the G 40 base Installation and Maintenance Manual An additional optical alarm signal of a detector or a group of detectors can be obtained by connecting the WZ 31 alarm indicator Alarm system cables are routed in accord...

Page 8: ...8 IK E301 001GB Fig 2 Clamps of base interoperating with DOT 4046 plug IK E301 001GB 05 2011 01 2012 ...