IK
‐
E301
‐
001GB
3
1
PURPOSE
The
DOT
‐
4046
multi
‐
sensor
addressable
smoke
and
heat
detector
is
designed
for
detection
of
a
fire
initial
phase
when
a
smoke
occurs
and/or
temperature
rise
may
be
observed.
The
detector
is
characterised
by
a
high
resistance
level
against
wind
movement
and
pressure
change.
The
DOT
‐
4046
multi
‐
sensor
addressable
detectors
are
intended
to
operate
in
the
POLON
4000
fire
detecting
and
alarm
system
control
panel
addressable
lines.
They
are
equipped
with
internal
short
circuit
isolators.
2
TECHNICAL
SPECIFICATIONS
Operating
voltage
16.5
V
÷
24.6
V
Maximum
current
draw
≤
150
µA
Maximum
installation
height
*)
7.5
m
Maximum
supervised
area
*)
40
m
2
Operating
temperature:
‐
for
‘1’
and
‘2’
modes
from
‐
25
°C
to
+50
°C
‐
for
‘3’
and
‘4’
modes
from
‐
25
°C
to
+65
°C
Allowable
relative
humidity
up
to
95
%
at
40
°C
Dimensions
(without
base)
Ø
115
mm
x
43
mm
Number
of
basic
operation
modes
4
Mass
(without
base)
0.2
kg
Standard
colour
white
Address
coding
method
programmable
at
the
control
panel
Test
fire
detection
suitability
TF1,
TF2,
TF3,
TF4,
TF5,
TF6,
TF8.
*)
see
design
guidelines
3
SAFETY
CONDITIONS
3.1
Repairs
and
maintenance
Any
maintenance
works
or
periodic
inspections
shall
be
executed
by
skilled
personnel
employed
by
companies
authorised
and
trained
by
POLON
‐
ALFA.
Any
repairs
must
be
carried
out
by
the
manufacturer.
POLON
‐
ALFA
bears
no
responsibility
for
the
operation
of
any
apparatus
being
repaired
by
unauthorised
personnel.
3.2
Works
at
height
Any
detector
installation
works
carried
out
at
height
must
be
executed
with
particular
care
utilising
tools
and
machinery
in
good
working
condition.
Special
attention
shall
be
given
to
stability
of
ladders,
elevators,
lifts,
etc.