background image

14

Figure 14: Input Graph

Gas Input Rate

The gas input rate of this water heater is affected by 

several environmental factors such as:

• 

The heating value of the gas

• 

The air and gas densities (which vary widely due to baro-

metric pressure and temperature changes)

• 

Venting installations (pipe diameter, length and fittings)

• 

Altitude

When measuring the input rate these factors should be 

incorporated into the calculations. Also measure the gas 

consumption over a sufficiently long time to obtain an 

accurate gas consumption rate (e.g. 3-5 minutes, not one 

revolution of the meter needle).
Long vents and each additional elbow, inherently reduce 

the gas input rate due to increased resistance to moving 

combustion air and flue gases. The approximate maximum/

minimum input for the 100k, 130k, and 150k models is 

shown in figure 14.

WATER PIPING SYSTEM

Piping Installation

Piping, fittings, and valves should be installed according to 

the installation drawing (figure 15). If the indoor installation 

area is subject to freezing temperatures, the water piping 

must be protected by insulation. 
The water supply pressure should not exceed 80 psi 

(551.5 kPa). If this occurs, a pressure reducing valve with a 

bypass should be installed in the cold water inlet line. This 

should be placed on the supply to the entire house in order 

to maintain equal hot and cold water pressures.

Important: Heat cannot be applied to the water fittings 

on the heater as they may contain nonmetallic parts. 

If solder connections are used, solder the pipe to the 

adapter before attaching the adapter to the hot and 

cold water fittings. 
Important:  Do not install this water heater with iron or 

galvanized piping.  Use brass caps on all unused inlet/

outlet connections.

 

1.  Install the water piping and fittings as shown in figure 

15. Note: If state or local codes require, install a vacu-

um relief valve per the manufactures instructions in the 

cold water supply line. Connect the cold water supply 

(use 1” NPT) to the fitting marked “COLD INLET”.  

Do not turn the cold water nipple. The mark should         

remain along the top side of the nipple. Connect the 

hot water supply (use 1” NPT) to the fitting marked 

“HOT OUTLET”. 

2.  Always use a suitable grade of joint compound and be 

certain that all fittings are tightened properly.

3.  The installation of unions in both the hot and cold water 

supply lines is recommended for ease of removing the 

water heater for service or replacement.

4.  If installing the water heater in a closed water system, 

install an expansion tank in the cold water line as speci-

fied under “Closed System/Thermal Expansion” (Page 

15).

5.  Install a shut-off valve in the cold water inlet line.  It 

should be located close to the water heater and be 

easily accessible. Know the location of this valve and 

how to shut off the water to the heater.

6. The 

Polaris

®

 gas water heater is shipped with a factory-

installed Temperature and Pressure Relief Valve.  

Install a discharge line in the opening in the T & P valve 

(see instructions on Page 17).

7.  After piping has been properly connected to the water  

heater, remove the aerator at the nearest hot water    

faucet.  Open the hot water faucet and allow the tank  

to completely fill with water. 

(To prevent damage to 

the unit, DO NOT connect power until the tank is 

COMPLETELY FILLED).

 To purge the lines of any  

excess air, keep the hot water faucet open for 3 min-

utes after a constant flow of water is obtained. Close 

the  faucet and check all connections for leaks.

Corrosion and Water Quality

Water quality will vary from location to location and may 

contain contaminates that may reduce the life or perfor-

mance of the water heater. To test for contaminates a 

water quality test kit is available, reference part number 

6903791.
Contaminates which can reduce the life or performance 

of the water heater if present in high quantities include 

those which contribute to hardness (dissolved minerals 

such as sodium, calcium and magnesium); plus chlorides 

and sulfates. Additionally, water that is too acidic or basic 

(measured as pH) can reduce the life of the water heater. 

Water treatment systems (such as water softeners for 

hardness) should be used and maintained properly if the 
contaminate levels exceed the following:

Warranty is void in applications which exceed the 

water quality requirements listed below.

Table 2:

Total Hardness:

12 grains per gal. (205 mg/liter) max.

Chloride:

200 mg/liter max.

pH:

6.5-8.0

Alkalinity:

200 mg/liter max.

Summary of Contents for PG 34-100-2NV or 2PV

Page 1: ...hbor s telephone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agenc...

Page 2: ...r these conditions we recommend the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance which is connected to the hot water system If hydrogen is p...

Page 3: ...orized service person The manufacturer and seller of this water heater will not be liable for any damages injuries or deaths caused by failure to comply with the installation and operating instruction...

Page 4: ...tally vented gas fueled heat ing appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The s...

Page 5: ...intain proper clearances as specified on the data plate Figure 1 Garage Installation Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance S...

Page 6: ...tolerance 1 9 cm 0 31 cm tolerance Note The trap should be aligned so that the exhaust pipe is in a vertical position close to the surface of the water heater Figure 2 Minimum Clearance Locations Back...

Page 7: ...ne into the metal drain pan VENT PIPE SYSTEM Carbon Monoxide Hazard Follow all instructions to locate and install the vent pipe system Instructions can be found in this manual in state or local codes...

Page 8: ...shell housing by turning clockwise approximately 1 2 30 5 cm and pulling off of the internal clamshell housing see figure 4C Using your fingers or a small flat blade screwdriver remove the filter medi...

Page 9: ...the specified CSA listed plastic vent pipe All joints in the inlet and outlet piping must be properly cemented Size and cut all piping before cementing 1 Cut the pipe end square and remove all ragged...

Page 10: ...tain a 36 in 91 cm minimum clearance below a window or door that may be opened C Clearance to permanently closed window D 12 in 30 cm min vertical clearance to ventilated soffit located above the term...

Page 11: ...Units on Page 12 for correct terminations if installing more than one Polaris gas water heater Alternative Horizontal Termination The combustion air and exhaust terminations may be raised up to 24 inc...

Page 12: ...ne or anticipated snow levels See figure 9 below Note See Venting Additional Polaris Units below if installing more than one Polaris gas water heater Venting Additional Polaris Units When using two 2...

Page 13: ...hrough the Roof Termination Notes 1 Support Horizontal Pipe Every Four Feet 1 2 m Support Vertical Pipe Every Six ft 1 8 m 2 Increase The 12 Inch 30 5 cm MinimumAbove Grade To Keep Inlet OpeningAboveA...

Page 14: ...supply use 1 NPT to the fitting marked HOT OUTLET 2 Always use a suitable grade of joint compound and be certain that all fittings are tightened properly 3 The installation of unions in both the hot...

Page 15: ...l contaminate the potable water supply Closed System Thermal Expansion As water is heated it expands thermal expansion In a closed system the volume of water will increase As the volume of water incre...

Page 16: ...the water heater should be ver tical past any mixing valve or supply line to the heating system to remove air bubbles from the system Do not connect the water heater to any system or components previo...

Page 17: ...ine Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Must not be capped blocked plugged or contain any valve between the relief...

Page 18: ...9 for gas piping installation 1 Install a readily accessible manual shut off valve in the gas supply line as recommended by the local utility Know the location of this valve and how to turn off the ga...

Page 19: ...onally listed recognized fuel gas and carbon monoxide CO detectors are recommended in all applications and should be installed using the manufacturer s instructions and local codes rules or regulation...

Page 20: ...electrical wiring to the water heater 1 Shut off the power at the electrical service box 2 Loosen the screws securing the access panel to the electrical compartment The electrical wiring diagram model...

Page 21: ...T L1 NEUTRAL GND PSI PSO PRESSURE SWITCH BLACK WHITE WHITE RED LED YELLOW LED GREEN LED BROWN YELLOW RED THERMOSTAT DIAL ORANGE GAS VALVE BROWN BLUE BLUE WHITE IGNITER RED GREEN YELLOW ORANGE RED 24V...

Page 22: ...1 8 per foot 10 5 mm per meter Away from corners other vents windows etc Alternate Horizontal Correct relationship outlet to inlet 12 Min 30 5 cm above anticipated snow level 2 exhaust outlet air inle...

Page 23: ...ich signals the beginning of the ignition sequence see figure 21 and Red Ignition control is signaling the gas valve to open Figure 21 Sequence of Operation When the thermostat calls for heat the blow...

Page 24: ...e thermostat is adjusted to its lowest temperature setting when it is shipped from the factory Water temperature can be regulated by moving the temperature dial to the preferred setting The preferred...

Page 25: ...eing shut down during freezing temperatures To drain the tank perform the following steps 1 Turn off the gas supply at the Manual Gas Shut off Valve Turn off the electrical supply to the water heater...

Page 26: ...Remove the gas valve from the unit keeping the rubber gasket with the gas valve 8 Remove the flange from the gas inlet side of the valve by removing the four 4 attachment screws Figure 25 Replacing t...

Page 27: ...arity Detection SC SL Soft Lockout Control Automatically resets after 60 minutes SL3 Soft Lockout Hard Lockout Control automatically resets after 60 minutes with a maximum of 3 resets followed by hard...

Page 28: ...28 SOFTWARE OPERATION SEQUENCE IGNITION CONTROL MODULE SOFTWARE OPERATION SEQUENCE...

Page 29: ...TE TRAP ASSEMBLY 32 COLD WATER TUBE ASSEMBLY 33 TEMPERATURE AND PRESSURE RELIEF VALVE 34 DRAIN VALVE 35 POTENTIOMETER 36 VENTURI GASKET not pictured 37 BLOWER ISOLATION RELAY TOOLS REQUIRED FOR SERVIC...

Page 30: ...15 3 4 40 1 2 41 6 3 8 5 1 2 6 5 8 150 PG 34 150 2NV OR 2PV 34 150 2 OR 3 48 1 2 22 15 3 4 40 1 2 41 6 3 8 5 1 2 6 5 8 150 PG 50 130 2NV OR 2PV 50 130 2 OR 3 62 3 8 22 15 3 4 54 1 2 55 6 3 8 5 1 2 6 5...

Page 31: ...31 NOTES...

Page 32: ...d To obtain technical warranty or service assistance during or after the installation of this water heater visit our website at http www americanwaterheater com or call toll free 1 800 456 9805 P O Bo...

Reviews: