Polaris PG 34-100-2NV or 2PV Use And Care Manual Download Page 23

23

OPERATING YOUR WATER HEATER

Read and understand these directions thoroughly before 
attempting to operate the water heater (see Operating 
Instructions on Page 24).  Check the data plate on the 
front of the water heater for the correct gas. Do not use this 
water heater with any gas other than the one listed on the 
data plate.  If you have any questions or doubts, consult 
your gas supplier or gas utility company.

L.P. (Propane) Models

Propane gas is heavier than air and in the occurrence of 
a leak in the system, the gas will settle on the floor level.  
Basements, crawl spaces, skirted areas under mobile 
homes (even when ventilated), closets and areas below 
ground level will serve as pockets for the accumulation of 
gas.  Before lighting a propane gas water heater, smell all 
around the appliance at floor level.  If you smell gas, follow 
the instructions as given in the warning on the front page.

When your propane tank runs out of fuel, turn off the gas 
at all gas appliances including pilot lights.  After the tank 
is refilled, all appliances must be re-lit according to their 
manufacturer’s instructions.

Water Heater Operation

This water heater does not have a pilot light.  It is equipped 
with an electronic ignition that automatically lights the 
burner.  There are three lights to indicate the various stages 
of operation;  

Green

 = Electrical power is on, 

Yellow

 = 

Thermostat is calling for heat, which signals the beginning 
of the ignition sequence (see figure 21), and 

Red

 = Ignition 

control is signaling the gas valve to open.

Figure 21: Sequence of Operation

When the thermostat calls for heat, the blower will run for 
6 seconds to purge the system of any accumulated gas or 
air.  The hot surface igniter will heat up for 35 seconds. The 
blower will turn on and the gas valve open, forcing the air 
and gas mixture across the hot surface igniter, causing the 
burner to light.  The hot surface igniter will turn off and act 
as an electronic flame sensor to determine if burner ignition 
has been accomplished.  If it detects any loss of flame, it 
will shut off the gas supply to the burner.
The ignition control will try to light the burner three times. 
If the ignition control does not detect a flame after three 
tries, it will temporarily lock out, but then auto restart and go 
through three additional tries for ignition after 60 minutes. 
It will repeat until ignition occurs or the system locks out 
requiring service. Refer to Troubleshooting Guide on Page 27.

Thermostat Sensor

The sensor is a 10K ohm [at 77°F (25°C)] thermistor.  Read 
resistance through the black wires that run to the sensor. 
Remove wires from circuit board before checking.  An open 
or short circuit indicates sensor failure.  Check reading 
against the values listed in Table 3.  The resistance should 
correspond with the temperature in the tank: 

Table 3:

                Temperature           

 

     

I

         Resistance

60°F

16°C

15,300 ohms

80°F

27°C

9,300 ohms

100°F

38°C

5,800 ohms

120°F

49°C

3,800 ohms

140°F

60°C

2,500 ohms

160°F

71°C

1,700 ohms

185°F

85°C

1,100 ohms

         

Summary of Contents for PG 34-100-2NV or 2PV

Page 1: ...hbor s telephone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agenc...

Page 2: ...r these conditions we recommend the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance which is connected to the hot water system If hydrogen is p...

Page 3: ...orized service person The manufacturer and seller of this water heater will not be liable for any damages injuries or deaths caused by failure to comply with the installation and operating instruction...

Page 4: ...tally vented gas fueled heat ing appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The s...

Page 5: ...intain proper clearances as specified on the data plate Figure 1 Garage Installation Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance S...

Page 6: ...tolerance 1 9 cm 0 31 cm tolerance Note The trap should be aligned so that the exhaust pipe is in a vertical position close to the surface of the water heater Figure 2 Minimum Clearance Locations Back...

Page 7: ...ne into the metal drain pan VENT PIPE SYSTEM Carbon Monoxide Hazard Follow all instructions to locate and install the vent pipe system Instructions can be found in this manual in state or local codes...

Page 8: ...shell housing by turning clockwise approximately 1 2 30 5 cm and pulling off of the internal clamshell housing see figure 4C Using your fingers or a small flat blade screwdriver remove the filter medi...

Page 9: ...the specified CSA listed plastic vent pipe All joints in the inlet and outlet piping must be properly cemented Size and cut all piping before cementing 1 Cut the pipe end square and remove all ragged...

Page 10: ...tain a 36 in 91 cm minimum clearance below a window or door that may be opened C Clearance to permanently closed window D 12 in 30 cm min vertical clearance to ventilated soffit located above the term...

Page 11: ...Units on Page 12 for correct terminations if installing more than one Polaris gas water heater Alternative Horizontal Termination The combustion air and exhaust terminations may be raised up to 24 inc...

Page 12: ...ne or anticipated snow levels See figure 9 below Note See Venting Additional Polaris Units below if installing more than one Polaris gas water heater Venting Additional Polaris Units When using two 2...

Page 13: ...hrough the Roof Termination Notes 1 Support Horizontal Pipe Every Four Feet 1 2 m Support Vertical Pipe Every Six ft 1 8 m 2 Increase The 12 Inch 30 5 cm MinimumAbove Grade To Keep Inlet OpeningAboveA...

Page 14: ...supply use 1 NPT to the fitting marked HOT OUTLET 2 Always use a suitable grade of joint compound and be certain that all fittings are tightened properly 3 The installation of unions in both the hot...

Page 15: ...l contaminate the potable water supply Closed System Thermal Expansion As water is heated it expands thermal expansion In a closed system the volume of water will increase As the volume of water incre...

Page 16: ...the water heater should be ver tical past any mixing valve or supply line to the heating system to remove air bubbles from the system Do not connect the water heater to any system or components previo...

Page 17: ...ine Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Must not be capped blocked plugged or contain any valve between the relief...

Page 18: ...9 for gas piping installation 1 Install a readily accessible manual shut off valve in the gas supply line as recommended by the local utility Know the location of this valve and how to turn off the ga...

Page 19: ...onally listed recognized fuel gas and carbon monoxide CO detectors are recommended in all applications and should be installed using the manufacturer s instructions and local codes rules or regulation...

Page 20: ...electrical wiring to the water heater 1 Shut off the power at the electrical service box 2 Loosen the screws securing the access panel to the electrical compartment The electrical wiring diagram model...

Page 21: ...T L1 NEUTRAL GND PSI PSO PRESSURE SWITCH BLACK WHITE WHITE RED LED YELLOW LED GREEN LED BROWN YELLOW RED THERMOSTAT DIAL ORANGE GAS VALVE BROWN BLUE BLUE WHITE IGNITER RED GREEN YELLOW ORANGE RED 24V...

Page 22: ...1 8 per foot 10 5 mm per meter Away from corners other vents windows etc Alternate Horizontal Correct relationship outlet to inlet 12 Min 30 5 cm above anticipated snow level 2 exhaust outlet air inle...

Page 23: ...ich signals the beginning of the ignition sequence see figure 21 and Red Ignition control is signaling the gas valve to open Figure 21 Sequence of Operation When the thermostat calls for heat the blow...

Page 24: ...e thermostat is adjusted to its lowest temperature setting when it is shipped from the factory Water temperature can be regulated by moving the temperature dial to the preferred setting The preferred...

Page 25: ...eing shut down during freezing temperatures To drain the tank perform the following steps 1 Turn off the gas supply at the Manual Gas Shut off Valve Turn off the electrical supply to the water heater...

Page 26: ...Remove the gas valve from the unit keeping the rubber gasket with the gas valve 8 Remove the flange from the gas inlet side of the valve by removing the four 4 attachment screws Figure 25 Replacing t...

Page 27: ...arity Detection SC SL Soft Lockout Control Automatically resets after 60 minutes SL3 Soft Lockout Hard Lockout Control automatically resets after 60 minutes with a maximum of 3 resets followed by hard...

Page 28: ...28 SOFTWARE OPERATION SEQUENCE IGNITION CONTROL MODULE SOFTWARE OPERATION SEQUENCE...

Page 29: ...TE TRAP ASSEMBLY 32 COLD WATER TUBE ASSEMBLY 33 TEMPERATURE AND PRESSURE RELIEF VALVE 34 DRAIN VALVE 35 POTENTIOMETER 36 VENTURI GASKET not pictured 37 BLOWER ISOLATION RELAY TOOLS REQUIRED FOR SERVIC...

Page 30: ...15 3 4 40 1 2 41 6 3 8 5 1 2 6 5 8 150 PG 34 150 2NV OR 2PV 34 150 2 OR 3 48 1 2 22 15 3 4 40 1 2 41 6 3 8 5 1 2 6 5 8 150 PG 50 130 2NV OR 2PV 50 130 2 OR 3 62 3 8 22 15 3 4 54 1 2 55 6 3 8 5 1 2 6 5...

Page 31: ...31 NOTES...

Page 32: ...d To obtain technical warranty or service assistance during or after the installation of this water heater visit our website at http www americanwaterheater com or call toll free 1 800 456 9805 P O Bo...

Reviews: