DC Inverter Monoblock Duct Type Air Conditioner Installation and Operation Manual
18
Table.3
Model
Power
Supply
Capability
of Air
Switch(A)
(Outdoor)
Minimum Sectional
Area Of Earth Wire
(Outdoor/Indoor)
(mm2)
VDVS-30A6A
220-240/
~
,50HZ
25
2.5/0.75
VDVU-12A6A
220-240/
~
,50HZ
16
1.5
(1) The specifications of the breaker and power cable listed in the table above are determined
based on the maximum power (maximum amps) of the unit.
(2) The specifications of the power cable listed in the table above are applied to the conduit-
guarded multi-wire copper cable (like, YJV copper cable, consisting of PE insulated wires and a
PVC cable jacket) used at 40°С and resistible to 90°С(
see IEC 60364-5-52
)
. If the working condition
changes, they should be modified according to the related national standard.
(3) The specifications of the breaker listed in the table above are applied to the breaker with the
working temperature at 40°С. If the working condition changes, they should be modified according
to the related national standard.
EPE30-A1
EPC12-A1
EPE30-A1
EPC12-A1