
9
DIMENSIONS AND CAPACITY DATA
Table 2 – CAPACITY, GAS AND ELECTRICAL CHARACTERISTICS
$SSUR[LPDWH&DSDFLW\
0DQLIROG3UHVVXUH
(OHFWULFDO&KDUDFWHULVWLFV
U.S. Gals.
Liters
Gas Type
“WC
kPA
9ROWV+]
Amperes
34
129
1DW/3
0
0
<7
50
189
1DW/3
0
0
<7
* The manifold pressure is the factory setting and is not adjustable. A negative pressure will be seen with just the blower running without
the Gas Control Valve open.
All models - Maximum Supply Pressure: 14 inches W.C. (3.48kPa)
Minimum Supply Pressure for Natural Gas: 3.50” (.87kPa)
Minimum Supply Pressure for Propane Gas: 8.00” (1.99kPa)
Minimum pressure must be maintained under both load and no load (dynamic and static) conditions.
Table 3 – RECOVERY CAPACITIES
Input
5HFRYHU\&DSDFLWLHV
Rating
%WXKU
Rating
(kW)
Temp.
Rise
F
30
40
50
60
70
80
90
100
110
120
130
140
C
17
22
28
33
39
44
50
56
61
67
72
78
100,000
29.3
GPH
381
286
229
190
163
143
127
114
104
95
88
82
LPH
1442
1082
865
721
618
541
481
433
393
361
333
309
130,000
38.1
GPH
495
371
297
248
212
186
165
149
135
124
114
106
LPH
1875
1406
1125
937
803
703
625
562
511
469
433
402
150,000
44.0
GPH
571
429
343
286
245
214
190
171
156
143
132
122
LPH
2163
1622
1298
1082
927
811
721
649
590
541
499
464
175,000
51.3
GPH
667
500
400
333
286
250
222
200
182
167
154
143
LPH
2524
1893
1514
1262
1082
946
841
757
688
631
582
541
199,000
58.3
GPH
758
569
455
379
325
284
253
227
207
190
175
162
LPH
2870
2152
1722
1435
1230
1076
957
861
783
717
662
615
5HFRYHU\FDSDFLW\EDVHGRQWKHUPDOHI¿FLHQF\