Page 9 of 25
E02
System
Shutdown
Phase Loss
Phase Loss
Check whether the three-phase wiring of
power supply is correct
E03
System
Shutdown
Water
Flow
Switch
1
Protection
Water Flow Switch 1 open for 3
times in 1 hour
Check Water Flow Switch , water pump and
water pipe
E05
System
Shutdown
High Pressure Switch 1
Protection
High Pressure Switch 1 open for
3 times in 1 hour
Check manometers, heat exchangers, water
pump and water pipe
E06
System
Shutdown
Low Pressure Switch 1
Protection
Low Pressure Switch 1 open for
3 times in 1 hour
Check refrigerant, heat exchangers, and fan
motors
E07
System
Shutdown
High Pressure Switch 2
Protection
High Pressure Switch 2 open for
3 times in 1 hour
Check manometers, heat exchangers, water
pump and water pipe
E08
System
Shutdown
Low Pressure Switch 2
Protection
Low Pressure Switch 2 open for
3 times in 1 hour
Check refrigerant, heat exchangers, and fan
motors
E09
System
Shutdown
Communication Error
Communication failure between
mainboard and display panel
Check
communication
wire
sequence,
connector and type
E10
System
Shutdown
Insufficient
Water
Protection
Low Water Level Switch open for
10 minutes
Check low water level switch,water pump
and water level in the tank
E11
System
Shutdown
Time Limitation Protection
Consult the manufacturer when
the probation period expires
Enter the correct password to unlock
E12
System
Shutdown
Discharge gas temp 1
protection
Discharge gas temperature 1
exceeds the setting
Check if discharge gas temperature exceeds
the setting
E13
System
Shutdown
Discharge gas temp 2
protection
Discharge gas temperature 2
exceeds the setting
Check if discharge gas temperature exceeds
the setting
E15
System
Shutdown
Water tank temp sensor
failure
Sensor short or open
Secure connector or replace sensor
E16
Failure
report
Evaporator
coil
temp
sensor 1 failure
Sensor short or open
Secure connector or replace sensor
E17
Failure
report
Evaporator
coil
temp
sensor 2 failure
Sensor short or open
Secure connector or replace sensor
E18
Failure
report
Discharge
gas
temp
sensor 1 failure
Sensor short or open
Secure connector or replace sensor
E19
Failure
report
Discharge
gas
temp
sensor 2 failure
Sensor short or open
Secure connector or replace sensor
E21
Failure
report
Ambient
temp
sensor
failure
Sensor short or open
Secure connector or replace sensor
E22
Failure
report
Return water temp sensor
failure
Sensor short or open
Secure connector or replace sensor
E23
Failure
report
Inlet water temp sensor
failure
Sensor short or open
Secure connector or replace sensor
E25
System
Shutdown
Water level switch failure
Water level switches misplaced
Place the switches in the correct positions
E26
System
Shutdown
Outlet
water
over
temperature protection
Outlet
water
temperature
exceeds setting
Check pipeline filter, valve and water pump
head
E27
Failure
report
Outlet water temp sensor
failure
Sensor short or open
Secure connector or replace sensor
E28
System
Shutdown
Insufficient water flow
Differential
temp
inlet/outlet
exceeds setting
Check water flow, water circuit and water
pump head
E29
Failure
report
Suction temp sensor 1
failure
Sensor short or open
Secure connector or replace sensor