Page 24 of 25
L04
Action interval of electronic expan
sion valve
30sec
5
~
90
20
L05
Superheat value in cooling mode
0
-20
~
60
L06
Reserved
0
-20
~
60
L07
Minimum openings of EEV in coo
ling mode
64
10
~
250
Value*2=number of pulses
L08
Initial openings of main EEV in h
eating
160
10
~
250
Value*2=number of pulses
L09
Initial openings of main EEV in c
ooling
160
10
~
250
Value*2=number of pulses
L10
EEV High Discharge Gas Temper
ature
100
℃
80
~
120
L11
EEV Secondary Discharge Gas T
emperature
90
℃
70
~
110
L12
EEV High Suction Temperature
28
℃
10
~
60
L13
EEV High Temperature Superheat
-4
-20
~
60
L14
EEV High Ambient Temperature
26
℃
0
~
60
L15
EEV High Water Temperature
52
℃
5
~
80
L16
Auxiliary EEV Initial Opening
32
10
~
250
Value*2=number of pulses
L17
Auxiliary EEV Minimum Opening
8
8
~
250
Value*2=number of pulses
L18
Auxiliary EEV Superheat
0
-20
~
60
L19
High Temperature Overheat of Au
xiliary Circuit
0
-20
~
60
L20
Interval Time for Auxiliary EEV A
djustment
30
秒
5
~
90
L21
Discharge Gas Temp to Open Au
xiliary EEV
95
℃
20
~
110
Set to 110 to cancel this function
L22
A Zone Main Circuit Superheat
8
-20
~
60
Hot Water/Heating only
L23
B Zone Main Circuit Superheat
8
-20
~
60
Hot Water/Heating only
L24
C Zone Main Circuit Superheat
7
-20
~
60
Hot Water/Heating only
L25
D Zone Main Circuit Superheat
5
-20
~
60
Hot Water/Heating only
L26
E Zone Main Circuit Superheat
3
-20
~
60
Hot Water/Heating only
L27
A Zone Minimum Opening
44
10
~
250
Hot Water/Heating only, Value*2=number of pulses
L28
B Zone Minimum Opening
44
10
~
250
Hot Water/Heating only, Value*2=number of pulses
L29
C Zone Minimum Opening
52
10
~
250
Hot Water/Heating only, Value*2=number of pulses
L30
D Zone Minimum Opening
60
10
~
250
Hot Water/Heating only, Value*2=number of pulses
L31
E Zone Minimum Opening
80
10
~
250
Hot Water/Heating only, Value*2=number of pulses
L32
Reserved
5
1
~
30
L33
Reserved
32
10
~
250
L34
Auxiliary EEV maximum opening
240
0
~
250
L35
Reserved
0
0
~
250
Switch on / off setting
A01
High pressure switch protection
15
0
~
15
0[no]
、
1[yes]