Page 22 of 25
ng Mode
P02
Range of Maximum Temp In Hot
Water Mode
Range of Maximum Temp in Hea
ting Mode
6 0
℃
55
℃
3 0
~
85
25
~
80
Valid in Hot water Mode
Valid in Heating/Cooling Mode
P03
Differential Temp in Hot Water /H
eating Mode
5
℃
1
~
20
P04
Differential Temp in Cooling Mode
5
℃
1
~
20
P05
Temp compensation
2
℃
-5
~
15
P06
Differential Temp for make up wat
er
8
℃
0
~
30
Valid in hot water mode only
P07
Differential temp for stop make u
p water
4
℃
1
~
15
Valid in hot water mode only
P08
Set temp for return water
40
℃
10
~
50
P09
Ambient temp for electric heater
on
7
℃
-30
~
40
When it is set as 7
℃
,
the actual value is -20
℃
,
When it is set not as 7
℃
, the actual value is set
value -10
℃
P10
Differential temp for electric heate
r
7
℃
2
~
30
P11
Enthalpy increasing valve on amb
ient temp
10
℃
-9
~
60
P12
Discharge temp to turn on injectio
n valve
110
℃
10
~
125
P13
Differential temp for injection valv
e
15
℃
0
~
50
P14
Chassis heating on ambient temp
erature
5
℃
-9
~
21
Set to -9 to cancel this function
P15
Temperature for discharge pressur
e relief and fan shutdown
105
℃
10
~
130
Set to 130 to cancel this function
P16
Low pressure detection delay tim
e
5min
1
~
15
P17
Medium pressure switch protectio
n delay time
3min
1
~
15
P18
Chassis heating delay off time
20min
2
~
60
P19
Water level switch adjustment sen
sitivity
10
1
~
84
The higher the value is, the more sensitive the w
ater level switch is.
Protection parameter setting
B01
Compressor overcurrent protection
0
安
-20
~
45
Set to less than or equal to 0 to cancel this functi
on
B02
Discharge gas temperature protec
tion
115
℃
80
~
130
B03
Temperature difference-insufficient
water flow
15
℃
5
~
50
B04
Outlet water temperature too high
70
℃
50
~
90