Page 40 of 67
SK2018 CHV2-V/P-ECM-001
b)
MTV1 has stopped ≥ 10 min.
Note: Auto cool or auto heat operation are the same as cool or heat mode respectively.
Without Valve Configuration
COOL MODE
a)
Electric heater, AUX1, MTV1 and MTV2 are always off.
b)
If Tr ≥ Ts + 1ºC (or + 4ºC if economy contact is activated), then cool operation is activated and AUX2 is turned on. Indoor
fan runs at set speed.
c)
If Tr < Ts, then cool operation is terminated and AUX2 is turned off. Indoor fan runs at Modbus 310000 setting.
d)
The range of Ts is 16 - 30ºC
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
Note: When the unit is turned off, the indoor fan shut down after 5 seconds.
LOW TEMPERATURE PROTECTION OF INDOOR COIL
a)
If Ti1 ≤ 2ºC for 2 minutes, then AUX2 is turned off. If low speed is selected via user interface, then indoor fan runs at
medium speed. If medium or high speed is selected via user interface, then indoor fan runs at set speed.
b)
If Ti1 ≥ 5ºC for 2 minutes, then AUX2 is turned on. Indoor fan runs at set speed.
FAN MODE
a)
Indoor fan runs at the set speed while heater, AUX1, AUX2, MTV1 and MTV2 are turned off.
b)
Indoor fan speed can be adjusted to low, medium and high.
HEAT MODE
Heat mode without Electric Heater
a)
MTV1, MTV2, AUX2 and heater are always off.
b)
If Tr ≤ Ts - 1ºC (or - 4ºC if economy contact is activated), then heat operation is activated and AUX1 is turned on. Indoor
fan runs at the set speed.
c)
If Tr > Ts, then heat operation is terminated and AUX1 is turned off. Indoor fan runs at 200rpm.
d)
The range of Ts is 16 - 30ºC.
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
Heat mode with Electric Heater as booster
a)
MTV1, MTV2 and AUX2 are always off.
b)
If Tr ≤ Ts - 1ºC (or - 4ºC if economy contact is activated), then heat operation is activated and AUX1 is turned on. Indoor
fan runs at the set speed.
c)
If Tr > Ts, then heat operation is terminated and AUX1 is turned off. Indoor fan runs at Modbus 310000 setting.
d)
If Ti1 < 40ºC, then Electric Heater is turned on. If 40ºC ≤ Ti1 < 45ºC, then Electric Heater maintains its original state. If
Ti1 ≥ 45ºC, then Electric Heater is turned off.
e)
The range of Ts is 16 - 30ºC.
f)
Indoor fan speed can be adjusted to low, medium, high and auto.
PRE-HEAT
Pre-heat with Electric Heater
a)
Indoor fan will start after Electric Heater has been turned on for 10s.
POST-HEAT
Post-heat with and without Electric Heater
a)
AUX1 is off. Electric Heater is turned off.
b)
Indoor fan will stop after the unit has been turned off for 20secs.
Over heat protection of indoor coil in post-heat
a)
If Ti1 ≥ 75ºC, then AUX1 is turned off, indoor fan remains on and runs at high speed.
b)
If Ti1 < 70ºC, then AUX1 is turned on, indoor fan remains on and runs at set speed.
c)
If the indoor coil temperature sensor is damaged, then the protection mode will be overridden and the unit will work
according to the pre-heat and post-heat program.
DEHUMIDIFICATION MODE
a)
MTV1, MTV2, AUX1 and heater are always off.
b)
If Tr ≥ 25ºC, then indoor fan and AUX2 will be ON for 3 minutes, and then OFF for 4 minutes.
c)
If 16ºC ≤ Tr < 25ºC, then indoor fan and AUX2 will be ON for 3 minutes, and then OFF for 6 minutes.
d)
If Tr < 16ºC, then indoor fan and AUX2 will be turned off for 4 minutes.